93
31-00083—02
MornWarm
ubyte
1
The controller may receive a morning warm-up command from the
air equipment control so that the control will change to operate
with warm supply air. The morning warm-up types supported are
listed below:
0: MornMixedAir -Warm air is being supplied via the duct, the
temperature control is turned off, and either the damper Position or
air flow is commanded to a configurable set point.
1: MornWarmAir-Warm air is being supplied via the duct and the
temperature control is reverse acting. ReHeat may be turned on in
this configuration to supply warmer air to the space.
Reheat enabled
Peripheral heat enabled
2: MornWarmNoReheat-Warm air is being supplied via the duct
and the temperature control is reverse acting.
Reheat disabled
Peripheral heat enabled
TR
Temp-Delta
∆
F
3
∆
F Heating throttling range
2
≤
range
≤
30
∆
F
Precision: 0
Notes
The Tool will set the TR based on the value of the field “Reheat”.
IT
Time
sec
3100
sec Heating integral time
0
≤
range
≤
5000 sec
Precision: 0
Notes
The Tool will set the IT based on the value of the field “Reheat”.
DT
Time
sec
0
sec Modulating heating derivative time
0
≤
range
≤
9000 sec
Precision: 0
Table 23. Configuration Parameters (Continued)
NCI/Field
Net Data
Type
Default
Val
AP
Internal
Units
Description
Type
TR (F)
mod
5
1 stage
3
2 stage
4
3 stage
7
4 stage
8
Type
IT (sec)
mod
2400
1 stage
3100
2 stage
2500
3 stage
1650
4 stage
1200