Installation
4
DC1010/1020/1030/1040 Product Manual
8/05
2.2 Condensed
Specifications
Honeywell recommends that you review and adhere to the operating limits listed in Table
2-1 when you install your controller.
Table 2-1 Condensed Specifications
TECHNICAL DATA
Type of Input
TC (K, J, R, S, B, E, N, T, W, PL II, U, L)
RTD (Pt100
Ω
, JPt100
Ω
, JPt50
Ω
)
Linear (4 – 20mA)
Input Sampling Time
500 ms
PV Input
Input Resolution
14 bit (each)
PV/SP Indication
4-digit, 7 segment display
Constant Value Storage
System
Non-volatile memory (EEPROM)
Indication
Indication Accuracy
±
0.5%FS
Proportional Band (P)
0~200% (On/Off action at P=0)
Integral Time (I)
0~3600 sec (PD action at I=0)
Derivative Time (D)
0~900 sec (PI action at D=0)
Control Mode
Cycle Time
0~150 sec (4~20mA
Æ
0, SSR
Æ
1, relay
Æ
10)
Relay Output
Contact, SPST(DC1010)/SPDT(1020,1030,1040), 3A/240VAC
Voltage Output
Voltage Pulse, 20VDC/20mA
Linear Output
4~20mA, 0~5V, 0~10V, 1~5V, 2~10V
Motor Control Output
Three Position Step Control (Time proportional motor control)
Output
Others
1
ϕ
SSR, 3
ϕ
SSR, 1
ϕ
SCR, 3
ϕ
SCR
Channel
3 channels (optional)
Mode
17 alarm mode available
Alarm
Timer
Flicker alarm, continued alarm, on delay timer alarm
Output Signal
SP, PV
Aux. Output
Type of Output
4~20mA, 0~20mA, 0~5V, 0~10V, 1~5V, 2~10V
Type of Input
4~20mA, 0~20mA, 0~5V, 0~10V, 1~5V, 2~10V
2
nd
Input
(RSP)
Sampling Time
500 ms
Pattern/Segment
2 pattern/ 8 segment (each)
Program
Availability
Pattern link & repeat, program/segment end alarm
Communication
Type of Communication
RS-232, RS-485
Rated Power Supply
Voltage & Frequency
AC 100-240V, 50/60Hz or DC15-50V, 4VA
Power Consumption
Max. 8VA
Storage Temperature
-25
°
C~65
°
C
Ambient Temperature
0
°
C~50
°
C
General
Specifications
Ambient Humidity
50~85% RH (no condensation)
Summary of Contents for DC1000 SERIES