Configuration
8/05
DC1010/1020/1030/1040 Product Manual
29
4.3 ALARMS
CONFIGURATION
4.3.1 Alarm Function Selections
These Alarm Function Selections are entered in “Configuration 2”. See Section 4.2.1.
Table 4-3 Alarm Function Selections
Code
Description
Hold-ON
Refer to
00 / 10
None
01
Deviation high alarm
YES
Figure 4-2
11
Deviation high alarm
NO
Figure 4-3
02
Deviation low alarm
YES
Figure 4-4
12
Deviation low alarm
NO
Figure 4-5
03
Deviation high / low alarm
YES
Figure 4-6
13
Deviation high / low alarm
NO
Figure 4-7
04 / 14
Band alarm
NO
Figure 4-8
Figure 4-9
05
Absolute value high alarm
YES
Figure 4-11
15
Absolute value high alarm
NO
Figure 4-12
06
Absolute value low alarm
YES
Figure 4-13
16
Absolute value low alarm
NO
Figure 4-14
07
Segment end alarm
(Use for program model only)
- Paragraph
4.3.4.1
17
Program run alarm
(Use for program model only)
- Figure
4-15
08
System error alarm (On)
-
Figure 4-16
18
System error alarm (Off)
-
Figure 4-17
19
Soak timer
-
Paragraph
4.3.5.3
“Hold-On”(Blocking)
means that the alarm does not work at the first time. The alarm
signal is suppressed until the parameter gets to the non-alarm limit or band.