Programmer (Optional)
42
DC1010/1020/1030/1040 Product Manual
8/05
Alarm Operation:
During the program running, Alarm 1 will become actuated
5.4.2
Segment Completion Alarm
ALD1
(Alarm Code for Alarm 1)= 07 (Segment End Alarm)
AL1
(Alarm Condition)= 2 (‘2’ means Segment No.) When segment 2 ends, AL1 will
act.
ALT1
(Alarm Time) = 00.10
Alarm Operation Example:
Once Segment 2 is completed, Alarm 1 will become actuated
and will be on for 10 seconds
5.4.3 END
Function
The DC1000
does not have an END segment
, so that the program will complete all the
segments if segments are defined. If the program procedure is less than 8 segments, set
the ‘OUT’ of next segment to 0, then the program running will be ended right after the
previous segment is completed. Otherwise, it will proceed for 8 or 16 segments
5.4.4 Linking
Function
The program function of DC1000 has 2 program patterns, and each program has a
maximum of 8 segments. You can link these two patterns to obtain a program of 16
segments (PTN = 0)
PTN
=1 proceed pattern 1-contains 8 segments.
PTN
=2 proceed pattern 2-contains 8 segments.
PTN
=0 linking proceed pattern 1 and 2 - total 16 segments.*
(*Please configure PTN1 and PTN2 first, and then set PTN to 0 – See Table 5-3 Program
Configuration Prompts)
5.4.5 Wait
Function
Refer to “Wait” in Table 4-2 for Setting.
Wait = 0
No Wait
Wait = Others
Program holds on WAIT state until PV > (SV – WAIT setting)
Example:
PV = 80
SV_1 = 100
WAIT = 2
When PV runs to 100 at segment 1, the program will hold until the PV > 98, then the
program will run to segment 2.
continued