Configuration
30
UDC3300 Basic Model: DC330B User Manual
5/00
3.9 Input 2 Parameters Set Up Group
Table 3-8 Input 2 Group Function Prompts
Function
Prompt
Lower Display
Function
Name
Selections or
Range of Setting
Upper Display
Factory
Setting
IN2 TYPE
Input 2 Actuation Type
For Input Range
Minimum and Maximum
see Appendix E
DISABL
NM90 L
500 PT
B TC
NIC TC
RAD RH
E TC H
R TC
RAD RI
E TC L
S TC
0-20mA
J TC H
T TC H
4-20mA
J TC L
T TC L
0-10mV
K TC H
W TC H
0-50mV
K TC L
W TC L
0-5 V
NNM H
100 PT
1-5 V
NNM L
100 LO
0-10 V
NM90 H
200 PT
SLIDEW
0-10mV
XMITTER2
Transmitter
Characterization
B TC
S TC
E TC H
T TC H
E TC L
T TC L
J TC H
W TC H
J TC L
W TC L
K TC H
100 PT
K TC L
100 LO
NNM H
200 PT
NNM L
500 PT
NM90 H
RAD RH
NM90 L
RAD RI
NIC TC
LINEAR
R TC
SQROOT
LINEAR
IN2 HI
Input 2 High Range Value
(Linear Inputs only)
–999. to 9999. floating
(in engineering units)
1000
IN2 LO
Input 2 Low Range Value
(Linear Inputs only)
–999. to 9999. floating
(in engineering units)
0
RATIO 2
Input 2 Ratio
–20.00 to 20.00
1.000
BIAS IN2
Input 2 Bias
–999. to 9999.
(in engineering units)
0
FILTER 2
Input 2 Filter
0 to 120 seconds
1
BURNOUT2
Burnout Protection
NONE
DOWN
UP
NO_FS
NONE
EMISSIV2
Emissivity
0.01 to 1.00
0.00
Summary of Contents for DC3300
Page 1: ...Sensing and Control UDC3300 Basic Model DC330B User Manual 51 52 25 78 5 00 ...
Page 26: ...Installation 18 UDC3300 Basic Model DC330B User Manual 5 00 ...
Page 70: ...Setpoint Rate Ramp Soak Program Operation 62 UDC3300 Basic Model DC330B User Manual 5 00 ...
Page 72: ...Environmental and Operating Conditions 64 UDC3300 Basic Model DC330B User Manual 5 00 ...
Page 74: ...Model Selection Guide 66 UDC3300 Basic Model DC330B User Manual 5 00 ...
Page 80: ...Position Proportional Calibration 72 UDC3300 Basic Model DC330B User Manual 5 00 ...
Page 82: ...Input Ranges 74 UDC3300 Basic Model DC330B User Manual 5 00 ...
Page 83: ......