Setpoint Rate/Ramp/Soak Program Operation
58
UDC3300 Basic Model: DC330B User Manual
5/00
500
400
200
300
°F
Time/
Hours
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
SEG 2
SEG 3
SEG 4
SEG 5
SEG 6
SEG 7
SEG 8
SEG 9
SG 10
SG 11
SG 12
SEG 1
22624
Figure 5-1 Ramp/Soak Profile Example
Prompt
Function
Segment
Value
Prompt
Function
Segment
Value
STRT SEG
Start Seg.
1
SEG4TIME
Soak Time
4
1 hr.
END SEG
End Seg.
12
SEG5RAMP
Ramp Time
5
1hr.:30min.
RAMP UNIT
Engr. Unit
for Ramp
TIME
SEG6 SP
Soak SP
6
250
RECYCLES
Number of
Recycles
2
SEG6TIME
Soak Time
6
3hr.:0min.
SOAK DEV
Deviation
Value
0
SEG7RAMP
Ramp Time
7
2hr.:30min.
PROG END
Controller
Status
LAST SP
SEG8 SP
Soak SP
8
500
STATE
Controller
State at end
HOLD
SEG8TIME
Soak Time
8
0hr.:30min.
KEYRESET
Reset SP
Program
DISABL
SEG9RAMP
Ramp Time
9
0
HOTSTART
PV Hot
Start
Program
Initialization
or power up
in SPP
DISABL
SG10 SP
Soak SP
10
400
SEG1RAMP
Ramp Time
1
1 hr.
SG10 TIME
Soak Time
10
0hr.:30min.
SEG2 SP
Soak SP
2
300
SG11RAMP
Ramp Time
11
3hr.:30min.
SEG2TIME
Soak Time
2
1hr.:30min.
SG12 SP
Soak SP
12
200
SEG3RAMP
Ramp Time
3
1hr.
SG12TIME
Soak Time
12
0hr.:30min.
SEG4 SP
Soak SP
4
400
Summary of Contents for DC3300
Page 1: ...Sensing and Control UDC3300 Basic Model DC330B User Manual 51 52 25 78 5 00 ...
Page 26: ...Installation 18 UDC3300 Basic Model DC330B User Manual 5 00 ...
Page 70: ...Setpoint Rate Ramp Soak Program Operation 62 UDC3300 Basic Model DC330B User Manual 5 00 ...
Page 72: ...Environmental and Operating Conditions 64 UDC3300 Basic Model DC330B User Manual 5 00 ...
Page 74: ...Model Selection Guide 66 UDC3300 Basic Model DC330B User Manual 5 00 ...
Page 80: ...Position Proportional Calibration 72 UDC3300 Basic Model DC330B User Manual 5 00 ...
Page 82: ...Input Ranges 74 UDC3300 Basic Model DC330B User Manual 5 00 ...
Page 83: ......