Chapter 7. PARAMETER SETUP
7-18
■
Event configuration data settings “
E
v
”
No.
Item Code
Item
Factory
User
Setting
Setting
Setting
1
E
T
1
0
2
E
D
1
0
3
H
Y
S
1
5
4
D
L
1
0
PV type events
0: PV direct
1: PV reverse
2: Deviation direct
3: Deviation reverse
4: Absolute value deviation1 direct
5: Absolute value deviation1 reverse
6: SP direct
7: SP reverse
8: MV direct
9: MV reverse
10: MFB direct
11: MFB reverse
12 to 49: NOP
Time events
50: Time event
51 to 99: NOP
Controller status events
100: RUN+HOLD+FAST+END
101: READY
102: RUN
103: HOLD
104: FAST
105: END
106: G.Soak standby
107: MANUAL
108: Auto-tuning executing
109: Constant-value operation
110: MFB estimated position control
111: Sum of all alarms
112: PV range alarm
113: Controller alarm
114: Low battery voltage
115: Console setup in progress
116: Loader setup in progress
117: ADV (ON time 1s)
118 to 199: NOP
[Note]
Setting can be changed only in READY mode.
0: Standby OFF
1: Standby ON
[Note]
The controller stands by after power is restored and in
the READY mode. When the event type setting is
≥
50,
“– – – –” is displayed and setting is not possible.
0 to 200U (when event type is neither MV nor MFB)
0.0 to 20.0% (when event type is MV or MFB)
[Note]
When the event type setting is
≥
50, “– – – –” is
displayed and setting is not possible.
0 to 3600s
Event 1 type
Event 1 standby
Event 1 hysteresis
Event 1 ON delay
time