Chapter 10. SPECIFICATIONS
10-6
Item
Specification
General
Specifica-
tions
Display characters
Isolation
Memory backup
Rated power voltage
Power consumption
Power ON rush current
Power ON operation
Allowable transient power
loss
Insulation resistance
Dielectric strength
Standard conditions
Operating conditions
Installation mode
Applicable standards
Installation category
Pollution degree
Char. bit count
Format
Data length
11bits/character
1 start bit, even parity, 1 stop bit; or 1 start bit, no parity, and 2 stop
bits
8bits
All inputs and outputs are completely isolated.
RS-485 communications can be performed by connecting to a computer equipped with an RS-485 interface.
Ambient temperature
Ambient humidity
Rated power voltage
Power frequency
Vibration resistance
Impact resistance
Mounting angle
Altitude
Ambient temperature
range
Ambient humidity range
Rated power voltage
Power frequency
Vibration resistance
Impact resistance
Mounting angle
Memory
Battery backed-up RAM
Battery life
Controller power OFF
Approx. 3 years under standard conditions
Controller power ON
Approx. 10 years under standard conditions
90 to 264Vac, 50/60Hz
30VA max.
15A max., 10ms (under operating conditions)
When starting up a number of DCP31s simultaneously, ensure ample power is supplied
or stagger startup times. Otherwise, the controllers may not start normally due to inrush
current induced-voltage drop. Voltage must stabilize within 2s after power ON.
Reset time:
15s max. (time until normal operation possible under normal operating
conditions)
20ms max. (under operating conditions)
Min. 20M
Ω
across power terminal (1) or (2) and ground terminal (3) (using a 500Vac
megger)
1500Vac 50/60Hz for 1min across power terminal and ground terminal
1500Vac 50/60Hz for 1min across relay output and ground terminal
500Vac 50/60Hz for 1min across non-power terminal and ground terminal
500Vac 50/60Hz for 1min across isolated terminals
23
±
2
°
C
60
±
5%RH
105Vac
±
1%
50
±
1Hz or 60
±
1Hz
0m/s
2
0m/s
2
Reference plane (vertical)
±
3
°
2000m max.
0 to 50
°
C (temperature at case bottom when closely mounted)
10 to 90%RH (no condensation)
90 to 264Vac
50
±
2Hz or 60
±
2Hz
0 to 1.96m/s
2
0 to 9.80m/s
2
Reference plane (vertical)
±
10
°
Handling Precautions
Permanently connected type controller, indoor installation, panel-mounted
EN61010-1, EN50081-2, EN50082-2 (CE statement), EN61326
Category II (IEC664-1, EN61010-1)
2