  OPERATING INSTRUCTIONS

74-5069

DeltaNet FS90 Operating Instructions

SYSTEM OPERATION

A normally functioning DeltaNet Fire & Security System is indicated 

by the green RUN and green POWER LEDs on the powered Control 

Board. If a Communication Board is installed, the Communication 

Board red TRANSMIT and RECEIVE LEDs blink as data is 

communicated.

Power Supply Supervision

The power supply circuits for the DeltaNet FS90 Fire & Security 

system are monitored for Integrity. Trouble conditions in these circuits 

are indicated by Low Battery (yellow) and Power (green) LEDs on the 

CA control board. In the normal, supervisory, condition, the yellow 

Low Battery LED is off and the green Power LED is on. A trouble 

condition in the power supply circuits is indicated when either the 

green Power LED is blinking or the yellow Low Battery LED is on. If 

this occurs, contact a service technician to determine the nature of the 

trouble condition by removing the batteries from the system and 

testing their condition. With the batteries out of the system, proper 

functioning of the power supply, battery changer and battery 

supervision circuits should be verified. Any faulty component must be 

replaced.

Modes of Operation

The DeltaNet Fire & Security System can operate independently 

(Stand-Alone Mode) or as a Data Gathering Panel (DGP) in a higher-

order system (DGP Mode). DGP Mode is in effect when a 

Communication Board is plugged into the Motherboard and active 

communication takes place. If communication fails, the system 

operates in Stand-Alone Mode.

LJ Communication/Display Board Switch

When the LJ Board MULTIPLE ALARM-TROUBLE LED is on, 

multiple abnormal conditions (alarm, trouble, prealarm) exist on AE 

Board loops. The LJ Board displays one address at a time, beginning 

automatically with the address of the highest-priority device.

An address remains displayed until a new, higher priority device goes 

into an abnormal condition or until the PREVIOUS/NEXT switch is 

pushed. Use the PREVIOUS/NEXT switch to display other addresses 

as follows.

PRINTER/DISPLAY ASSEMBLY AND LH INTERFACE BOARD 
OPERATING INSTRUCTIONS

The two front Printer/Display Assembly switches are:

— Printer On-Line Switch with integral LED.

— Paper Advance Switch.

LH Interface Board switches are:

— ACK—UP to acknowledge indicated point in LCD display.

— ALL PT/ALM SUM—UP to request All Point Log; DOWN to 

request Alarm Summary Log.

— PREVIOUS/NEXT—UP to revert LCD display to former point; 

DOWN to advance LCD display to subsequent point.

FRONT PANEL SWITCHES/LEDS
Control Board Switches

ACKNOWLEDGE

— Pushing the ACKNOWLEDGE switch silences the local audible 

and changes blinking LEDs to ON. The ACKNOWLEDGE switch 

does not affect indicating zone outputs and does not silence alarm 

signals. Pushing the ACKNOWLEDGE switch acknowledges all 

alarms present in the panel.

— If the panel is a DGP, the ACKNOWLEDGE switch does not 

function when the DGP is communicating with the higher-order 

system. The ACKNOWLEDGE switch becomes functional when 

communication is broken.

SILENCE

Pushing the SILENCE switch does the following:

— Silences devices connected to indicating zones.

— Silences devices connected to Control Modules with indicating 

characteristic set.

— Silences the local audible.

— Turns on the Control Board SILENCE LED.

— Changes blinking LEDs to on.

RESET

Pushing the RESET switch removes power to all initiating zones for 

fifteen seconds and sends out a fifteen-second reset signal that 

returns all input-zone status indicators to normal. After reset, zones 

that return to alarm or trouble are annunciated as new alarms or 

troubles.

PANEL TEST

Performing a Panel Test reveals whether all boards are controlled by 

the panel microprocessor. Pushing the PANEL TEST switch turns on 

all LEDs, except Communication Board LEDs and turns on the local 

audible. A Panel Test does not interrupt alarms or troubles reporting in 

the system.

Pushing the PANEL TEST switch turns on all LJ Communication/

Display Board LEDs and causes the LJ Board to display the address 

8888.

Pushing the MANUAL EVACUATION switch does the following:

— Turns on all indicating zones.

— Turns on all AE Board Control Modules that have the indicating 

characteristic set during system setup.

— Causes a common alarm indication.

— Causes the local audible to pulse.

Manual evacuation is terminated by pushing either the SILENCE 

or the RESET switch.