SDC / DHC
Operation
EN2H-0221GE51 R0812
103
Para-
meter
Designation
Setting range / Setting values
Factory
setting
Setting
30*
OEM maximum
limit
Setting value of parameter 03 to
130 °C
110
31*
Full-load
regulation
OFF, 0.5 to 10
OFF
34
Power limit for
heating
50 ... 100 %
100
35
Power limit for hot
water
50 ... 100 %
100
37
Burner counter
mode (counter of
operating hours)
AUTO
AUTO
1
Feedback only
2
Free counter
38
Outside
temperature
lock, inverse
OFF, –20 to +30 °C
OFF
39
Fixed delay
(Cascade)
Off, 1...300min
OFF
RESET
ST-1
Resetting of burner
start counter and
operating hours of
stage 1 (not if
parameter 01 =
OFF)
SET by pressing the input button
–
RESET
ST-2
Resetting of
burner start
counter and
operating hours of
stage 2 (not if
parameter 01 = 2
or 01 = OFF)
SET by pressing the input button
–
* OEM
5.4.7 "District hot water" menu (DIST.HEATING)
The parameters in this menu refer to the type of the respective
district hot-water station and the associated specific control
functions.