Operation
SDC / DHC
104
EN2H-0221GE51 R0812
Para-
meter
Designation
Setting range / Setting values
Factory
setting
Setting
01
Increase
OFF, –10 to 50 K
0
02
Maximum limit of
flow temperature
setpoint
10 ... 130
°
C
90
03*
Minimum district
heating valve
stroke
0 ... 50 %
10
04
Secondary flow
boost
0,1 ... 30 %/K
5
05
Adjustment time
0 ... 60 min
3
06
Runtime of district
heating valve 1
10 ... 1800 s
120
07*
Runtime of district
heating valve 2
10 ... 1800 s
30
08
Maximum return
temperature
setpoint
0 ... 100
°
C
90
09
Application point
variable district
heating return
temperature
OFF, –40 to +10
°
C
OFF
10
Maximum return
temperature
setpoint with hot
water circuit
charge
0 ... 100
°
C
90