SDC / DHC
Operation
EN2H-0221GE51 R0812
109
Para-
meter
Designation
Setting range / Setting values
Factory
setting
Setting
10
Buffer operating
mode
1
Heating circuit
charge regulation
and hot-water circuit
1
2
Heating circuit
charge regulation
without hot-water
circuit
3
Heating circuit and
hot-water circuit
discharge regulation
4
Heating circuit
discharge regulation
without hot-water
circuit
5
Charge regulation
with hot-water circuit
switchover
6
Discharge regulation
for heat generator
11
Follow-up time of
buffer charging
pump
0 ... 60 min
3
5.4.12 "Total flow regulation" menu (MAIN SUPPLY)
The parameters in this module refer to special settings with regard
to total flow regulation.
This selection is only available if a total flow sensor is configured
on one of the variable inputs (see the "Hydraulics" menu,
parameters 08, 09 or 10).
Para-
meter
Designation
Setting range / Setting values
Factory
setting
Setting
01
Regulation
0 ... 50 %/K
5
03
Regulation
1 ... 600 s
180