Hydraulic Components
SDC / DHC
166
EN2H-0221GE51 R0812
7.3.1.6 Heating circuit temperature offset
For special applications this function offers the possibility to admit
the heating curve of the direct heating circuit with a constant
offset value. The demand value plus the offset value is
transmitted to the heat generator.
The displacement of the heating curve is carried out in parallel
with the flow temperature.
To ensure the desired setpoint temperature for remote heating
circuits as well.
5.4.4 "Direct heating circuit" menu (UNMIXED CIRC), Pg. 92
7.3.1.7 Heating circuit pump extended running time
The heating circuit pump ceases operation if there is no heat
demand from the heating circuit. Safety switch-off of the heat
generator is prevented.
While the pump extended running of a mixed heating circuit pump
(MC-1 and MC-2 only) is active, the mixed heating circuit
continues to adjust its setpoint without forwarding a demand value
to the heat generator.
5.4.4 "Direct heating circuit" menu (UNMIXED CIRC), Pg. 92
7.3.1.8 Screed function
This function is not active if the heating circuit control is used as
constant control (CC).
If the screed function is active for a direct heating circuit, only
requests of this heating circuit are forwarded to the heat
generator. Requests of other heating circuits are suppressed.
Activation of the screed function for a non-mixed heating circuit
only functions at the direct heating circuit of the central device
with address 10 (CD1 - DHC) and only if no other central devices
are present on the bus network.
Function
Application
See also
Function
See also
NOTE
Summary of Contents for DHC
Page 1: ...EN2H 0221GE51 R0812 Smile SDC heating and district heating controller SERVICE MANUAL ...
Page 2: ...EN2H 0221GE51 R0812 ...
Page 10: ...Contents SDC DHC 10 EN2H 0221GE51 R0812 ...
Page 36: ...Operation SDC DHC 36 EN2H 0221GE51 R0812 Operating overview ...
Page 66: ...Operation SDC DHC 66 EN2H 0221GE51 R0812 ...
Page 261: ......