At this setting the room sensor is only used as a display device
without influencing the room temperature-related functions. The
operation of the wall device is possible without restrictions.
All system layouts that exclude room influence while the display of
the actual room temperature is still required (in contrast to setting
OFF).
5.4.4 "Direct heating circuit" menu (UNMIXED CIRC), Pg. 92
7.3.4.2 Heating circuit room factor
This function determines to what extent a deviation of the room
temperature from the setpoint affects the control of boiler flow
temperature.
If there is no difference between the desired (TARGET) and the
current (ACTUAL) room temperature, the direct heating circuit's
flow temperature is controlled according to the set heating curve.
If there is a difference between the room temperature and the
setpoint, the heating curve is shifted parallel to the room
temperature axis so that the deviation is compensated. The
amount of the displacement depends on the setting of the room
factor.
The following relation applies:
−
=
100
factor
Room
x
Deviation
t
setpoin
room
Set
t
setpoin
room
Corrected
Example:
set room setpoint = 21°C
actual room temperature = 20°C
Deviation = -1 K
For a room influence of 100%:
C
x
K
C
t
setpoin
room
Corrected
°
=
−
−
°
=
22
100
100
1
21
The boiler temperature is controlled according to a heating curve
which corresponds to a room temperature setpoint of 22°C.
Application
See also
Function
Summary of Contents for DHC
Page 1: ...EN2H 0221GE51 R0812 Smile SDC heating and district heating controller SERVICE MANUAL ...
Page 2: ...EN2H 0221GE51 R0812 ...
Page 10: ...Contents SDC DHC 10 EN2H 0221GE51 R0812 ...
Page 36: ...Operation SDC DHC 36 EN2H 0221GE51 R0812 Operating overview ...
Page 66: ...Operation SDC DHC 66 EN2H 0221GE51 R0812 ...
Page 261: ......