Hydraulic Components
SDC / DHC
208
EN2H-0221GE51 R0812
Buffer control mode
1
2
3
4
5
6
Buffer loading pump
function if heat
generator is not
available and buffer
start-up protection is
active
–
–
OFF
OFF
–
–
Buffer loading pump
function if heat
generator is not
available and buffer
start-up protection is
not active
–
–
ON
ON
–
–
Action of heating
generator start-up
protection on heating
circuits (HDCP, MC1,
MC2):
No
No
Yes
Yes
No
Yes
Action of heat
generator start-up
protection on hot-water
circuit (tank loading
pump)
No
Yes
Yes
Yes
No
Yes
Action of heat
generator start-up
protection on buffer
loading pump
Yes
Yes
No
No
Yes
No
Summary of Contents for DHC
Page 1: ...EN2H 0221GE51 R0812 Smile SDC heating and district heating controller SERVICE MANUAL ...
Page 2: ...EN2H 0221GE51 R0812 ...
Page 10: ...Contents SDC DHC 10 EN2H 0221GE51 R0812 ...
Page 36: ...Operation SDC DHC 36 EN2H 0221GE51 R0812 Operating overview ...
Page 66: ...Operation SDC DHC 66 EN2H 0221GE51 R0812 ...
Page 261: ......