SDC / DHC
Technical data
EN2H-0221GE51 R0812
253
8.1.1 Installation recommendations
Mains voltage lines
(mains connection, burners, pumps, servo motors):
Diameter
1.5 mm
2
Max. permissible length
No limit for installation in buildings.
Safety low-voltage lines
(sensors, ext. switches upon demand via switching contact, modem connection lines, analog
signal lines etc.)
Diameter
0.5 mm
2
Max. permissible length
100 m (looped circuit); longer connection lines should be avoided
to prevent the risk of interference
Data bus lines
Diameter
0.6 mm
2
Max. permissible length
50 m (looped circuit, longest distance between a central device
and a device to be supplied); longer connection lines should be
avoided to prevent the risk of interference.
Recommended layouts
J-Y(St)Y 2 x 0.6
8.2 Sensor resistance values
8.2.1 NTC 20
For outside sensor (OT), heat generator sensor (BLRS/BS), tank
sensor (DHWS), mixed heating circuit 1 flow sensor (VF1), mixed
heating circuit 2 flow sensor (VF2), variable input 1 (VI-1) (setting
not for exhaust gas sensor), variable input 2 (VI-2), variable input 3
(VI-3), collector tank/buffer sensor (SBUS).^
°C
Ω
°C
Ω
°C
Ω
°C
Ω
°C
Ω
-50.0 1659706
-9.0
115575
31.0
15180
71.0
2989
111.0
793.7
-49.0 1541379
-8.0
109189
32.0
14511
72.0
2882
112.0
770.3
-48.0 1432919
-7.0
103194
33.0
13875
73.0
2779
113.0
747.7
-47.0 1332091
-6.0
97564
34.0
13270
74.0
2681
114.0
725.8
-46.0 1238358
-5.0
92274
35.0
12695
75.0
2587
115.0
704.7
-45.0 1153525
-4.0
87303
36.0
12148
76.0
2496
116.0
684.2
-44.0 1073429
-3.0
82628
37.0
11627
77.0
2409
117.0
664.5
-43.0
999894
-2.0
78232
38.0
11131
78.0
2325
118.0
645.3
-42.0
932327
-1.0
74094
39.0
10659
79.0
2245
119.0
626.9
-41.0
869327
0.0
70200
40.0
10210
80.0
2168
120.0
609.0
-40.0
814000
1.0
66515
41.0
9781
81.0
2094
121.0
591.7
-39.0
759391
2.0
63046
42.0
9373
82.0
2022
122.0
575.0
-38.0
708806
3.0
59777
43.0
8983
83.0
1954
123.0
558.8
Summary of Contents for DHC
Page 1: ...EN2H 0221GE51 R0812 Smile SDC heating and district heating controller SERVICE MANUAL ...
Page 2: ...EN2H 0221GE51 R0812 ...
Page 10: ...Contents SDC DHC 10 EN2H 0221GE51 R0812 ...
Page 36: ...Operation SDC DHC 36 EN2H 0221GE51 R0812 Operating overview ...
Page 66: ...Operation SDC DHC 66 EN2H 0221GE51 R0812 ...
Page 261: ......