SDC / DHC
Operation
EN2H-0221GE51 R0812
89
5.4.3 "Hot-water circuit" menu (DHW)
This menu contains all parameters required to program the
hot-water circuit, except the switch time programs.
Para-
meter
Designation
Setting range / Setting values
Factory
setting
Setting
Hot
water
Hot water at night
10°C to normal hot-water
temperature
40
Legio
protect
ion day
Legionella
protection day
OFF
No legionella protection
OFF
Mon to
Sun
Legionella protection on
specified day of week
ALL
Legionella protection
every day
03
Legionella
protection time
00:00 ... 23:00 hours
02:00
04
Legionella
protection
temperature
10 °C to setting value of
parameter 06
65
05
Transducer for hot-
water circuit
1
Hot-water circuit
temperature sensor
1
2
Hot-water circuit
temperature controller
(thermostat)
06
Maximum
temperature limit
for hot water circuit
20°C to heat generator maximum
temperature
If parameter 07 = 7:
20 to 90°C.
In automatic mode, from hot-
water circuit minimum
temperature.
65