SDC / DHC
Operation
EN2H-0221GE51 R0812
97
Para-
meter
Designation
Setting range / Setting values
Factory
setting
Setting
11
Constant tem-
perature setpoint
(only if output was
set to constant
regulator)
10 ... 95°C
20
12
Minimum
temperature limit
10°C to setting value of
parameter 13
20
13
Maximum
temperature limit
Setting value of parameter 12 to
Setting value of parameter 30 in
"Heat generator" menu (OEM
maximum limit)
75
14
Temperature
increase of heating
circuit
–5 ... 20 K
Mixed
heating
circuit = 4
15
Follow-up time of
pump
0 ... 60 min
5
16
Screed function
OFF
OFF
1
Functional heating
2
Screed-drying heating
17
Return maximum
temperature limit
10 ... 90
°
C
90
18
P part X
P
1 ... 50 %/K
2
19*
Sampling time T
s
1 ... 600 s
20
20
I part T
n
1 ... 600 s
270
21
Actuator runtime
10 ... 600 s
120
22*
Actuator end
position function
1
Continuous control
signal in end position
1
2
Control signal
suppressed at end
position (actuator de-
energised)
23
Room control C-
factor (SDW 30
only)
1 ... 100
8