background image

69-1055—1

8

T8524C,D MULTISTAGE MICROELECTRONIC THERMOSTATS

3. Press the increase 

 key again to display the

software identification code.
(Example: 02 = software ID code 2)

M6791

M4866

M4867

4. Press the increase 

 key again to display the

software revision number.
 (Example: 001 = revision number 1)

5. Press the increase 

 key again to display the

EEPROM identification code.
(Example: 222 = EEPROM ID 222)

6. Press and hold the increase 

 and decrease 

keys together, until the room temperature is
displayed, to exit the System Test. The System Test
times out after five minutes without any key presses.

CHECKOUT

Outdoor Temperature Sensor
(Where Applicable)

Allow the outdoor temperature sensor to soak in the
outdoor air for a minimum of five minutes before taking a
reading. With an accurate thermometer (

±

1

°

F [

±

0.5

°

C]),

measure the temperature at the sensor location, allowing
time for the thermometer to stabilize before reading. Match
the thermometer reading to the outdoor temperature
display at the thermostat.

TROUBLESHOOTING GUIDE

Available on select models.

(Continued)

Symptom

Possible Cause

Action

Display will not
come on.

Thermostat is not being
powered.

Check that C terminal is connected to the system
transformer.

Check for 24 Vac between C and R or RH terminals.

If missing 24 Vac:

check if the circuit breaker is tripped—reset the
circuit breaker.

check if the system fuse is blown—replace the fuse.  

check if the power switch on the HVAC equipment is
in the Off position—set to the On position.

check wiring between thermostat and HVAC
equipment—replace any broken wires and tighten
any loose connections.

If 24 Vac is present, proceed with troubleshooting.

Temperature
display is incorrect.

Room temperature display has
been reconfigured.

Enter Installer Setup Number 37 and reconfigure the display.

Thermostat is configured for °F
or °C display.

a

Enter Installer Setup Number 14 and reconfigure the display.

Bad thermostat location.

Relocate the thermostat.

Temperature
settings will not
change. (Example:
Cannot set the  

The upper or lower temperature
limits were reached.  

Check the temperature setpoints:

Heating limits are 40 to 90°F (7 to 31°C)

Cooling limits are 45 to 99°F (9 to 37°C) except T8524D 
cooling limits are 48 to 99°F

heating higher or
the cooling lower.)

The setpoint temperature range
stops were configured.

Check Installer Setup mode numbers 34 and 35 and
reconfigure the setpoint stops.

Summary of Contents for DMULTISTAGE T8524C

Page 1: ... your application 3 Installer must be a trained experienced service technician 4 After completing installation use these instructions to check out the product operation CAUTION Disconnect power supply to prevent electrical shock or equipment damage Location Install the thermostat about 5 ft 1 5m above the floor in an area with good air circulation at average temperature See Fig 1 Do not install th...

Page 2: ...ews into the holes 6 Tighten mounting screws WIRING All wiring must comply with local electrical codes and ordinances Refer to Fig 3 for typical hookups A letter code is located near each terminal for identification CAUTION Disconnect power before wiring to prevent electrical shock or equipment damage 1 Loosen the terminal screws on the wallplate and connect the system wires See Fig 4 IMPORTANT Us...

Page 3: ...A B PRESS LOWER EDGE OF CASE TO LATCH A ENGAGE TABS AT TOP OF THERMOSTAT AND WALLPLATE M6801 DISPLAY PRESENT SETTINGS AND SCROLL THROUGH INSTALLER SETUP MODES INFORMATION KEY i DECREASE TEMPERATURE SETTING INCREASE TEMPERATURE SETTING Using Thermostat Keys The thermostat keys are used to set temperature display present setting configure Installer Setup check System Test display outdoor temperature...

Page 4: ...ting To change between heat and cool press the Information i key until the setting to be changed appears INSTALLER SETUP NOTE For most applications the thermostat factory settings do not need to be changed Review the factory settings in Table 2 and if no changes are necessary go to the Installer System Test section The Installer Setup is used to customize the thermostat to specific systems Install...

Page 5: ...geover Not used 13 Degree temperature display 14 00 Temperature is displayed in F 01 Temperature is displayed in C Not used 15 thru 18 Extended fan operation in heatinga b 19 00 No extended fan operation after the call for heat ends 01 Fan operation is extended 90 seconds after the call for heat ends Extended fan operation in coolinga 20 00 No extended fan operation after the call for cool ends 01...

Page 6: ...nAuto System Fan Room Outdoor Em Ht Temporary Setting Wait Humid Aux Ht Remote Repl Batt M4844 M6792 TEST MODE NUMBER a Available on select models b T8524D is 48 F 9 C IMPORTANT Review the settings to confirm that they match the system INSTALLER SYSTEM TEST Use the Installer System Test to check the thermostat configurations and operation Refer to Table 3 for a list of the available system tests T...

Page 7: ...n T8524C 31 Stage one cool and system fan come on 32 Stage two cool comes on Stage one cool and system fan remain on 31 Stage two cool turns off 30 Stage one cool and system fan turn off Fan Equipment System test T8524D only i 40 Change from cooling to fan equipment system test 41 Fan comes on 40 Fan turns off Key or Switch Operation System test IMPORTANT Test Numbers will only be displayed when t...

Page 8: ...ill not come on Thermostat is not being powered Check that C terminal is connected to the system transformer Check for 24 Vac between C and R or RH terminals If missing 24 Vac check if the circuit breaker is tripped reset the circuit breaker check if the system fuse is blown replace the fuse check if the power switch on the HVAC equipment is in the Off position set to the On position check wiring ...

Page 9: ...pment replace any broken wires and tighten any loose connections If 24 Vac is present proceed with troubleshooting Thermostat minimum off time is activated Wait up to five minutes for the system to respond Enter Installer Setup mode number 33 Reconfigure minimum off time if required System selection is not set to Cool Set system selection to Cool Cooling setpoint is above room temperature Check co...