background image

E-MON INTERVAL DATA RECORDER

27

62-0394—06

Appendix K - Meter Limited Warranty 

Subject to the exclusions listed below, Honeywell E-Mon will either repair or replace (at its option) any product 
that it manufactures and which contains a defect in material or workmanship. 

The following exclusions apply: 

1.

This Limited Warranty is only effective for a period of (5) five years following the date of manufacture when 
installed in accordance with manufacturer’s instructions by qualified personnel.

2.

Honeywell E-Mon must be notified of the defect within ninety (90) days after the defect becomes apparent 
or known. 

3.

Buyer’s remedies shall be limited to repair or replacement of the product or component which failed to 
conform to Honeywell E-Mon’s express warranty set forth above. 

4.

Buyer shall be responsible for all freight costs and shall bear all risk of loss or damage to returned goods 
while in transit. 

5.

This Limited Warranty does not cover installation, removal, reinstallation, or labor costs, and excludes nor-
mal wear and tear. Buyer shall provide labor for the removal of the defective component or item and instal-
lation of its replacement at no charge to Honeywell E-Mon. 

6.

This Limited Warranty does not cover any product if: (i) a product is altered or modified from its original 
manufactured condition, (ii) any repairs, alterations or other work has been performed by Buyer or others 
on such item, other than work performed with Honeywell E-Mon’s authorization and according to its 
approved procedures; (iii) the alleged defect is a result of abuse, misuse, improper maintenance, improper 
installation, accident or the negligence of any party; (iv) damaged as a result of events beyond Honeywell 
E-Mon’s control or other force majeure events or (v) used in conjunction with equipment, components, 
accessories, parts or materials not supplied or approved by Honeywell E-Mon. 

7.

This Limited Warranty is limited to the obligation to repair or replace the manufactured product. THIS IS 
THE SOLE AND EXCLUSIVE REMEDY FOR ANY BREACH OF WARRANTY. IN NO EVENT SHALL HONEY-
WELL E-MON BE LIABLE FOR ANY INDIRECT, INCIDENTAL, SPECIAL, CONSEQUENTIAL OR PUNITIVE 
DAMAGES (INCLUDING ANY DAMAGE FOR LOST PROFITS) ARISING OUT OF OR IN CONNECTION WITH 
THE FURNISHING OF PRODUCTS, PARTS OR SERVICES, OR THE PERFORMANCE, USE OF, OR INABILITY 
TO USE ANY PRODUCTS, PARTS OR SERVICES, SALE OF OR OTHERWISE, WHETHER BASED IN CON-
TRACT, WARRANTY, TORT, INCLUDING WITHOUT LIMITATION, NEGLIGENCE, OR ANY OTHER LEGAL OR 
EQUITABLE THEORY. 

8.

EXCEPT AS EXPRESSLY PROVIDED HEREIN, HONEYWELL E-MON MAKES NO WARRANTY OF ANY KIND, 
EXPRESS OR IMPLIED WITH RESPECT TO ANY PRODUCTS, PARTS OR SERVICES PROVIDED BY HONEY-
WELL E-MON INCLUDING, BUT NOT LIMITED TO, THE IMPLIED WARRANTIES OF MERCHANTABILITY 
AND FITNESS FOR A PARTICULAR PURPOSE. PRODUCTS OR COMPONENTS DISTRIBUTED, BUT NOT 
MANUFACTURED, BY HONEYWELL E-MON ARE NOT WARRANTED BY HONEYWELL E-MON AND 
BUYER MUST INSTEAD RELY ON THE REPRESENTATIONS AND WARRANTIES, IF ANY, PROVIDED 
DIRECTLY TO THE BUYER BY THE MANUFACTURER OF SUCH PRODUCT OR COMPONENT.

Summary of Contents for E-Mon IDR Series

Page 1: ...INSTALLATION INSTRUCTIONS 62 0394 06 E Mon Interval Data Recorder ...

Page 2: ... 100 satisfied with your products we provide toll free technical and sales support Monday through Friday 8 00 am to 7 30 pm EST 800 334 3666 You may also reach us via email at info emon com If you have questions we can handle them quickly and effectively with a telephone call Please let us try to help you BEFORE you remove your meter And to help us help you we ask that you have all relevant inform...

Page 3: ...cations 12 Section 8 0 Protocol Definitions 13 Appendix A DIP Switch Settings 20 Appendix B Cable Configuration 20 Appendix C LED Indicator Locations 21 Appendix D IDR Circuit Board Components 21 Appendix E System Wiring Guides 22 Appendix F System Wiring Guides 23 Appendix G Modem System Configuration Diagrams 24 Appendix H Hard Wired System Configuration Diagrams 24 Appendix I Hard Wired System ...

Page 4: ...closed once installed Exposing the internal circuits to dust dirt fumes or high humidity can damage the IDR NOTE All internal circuits are isolated from the AC line IDR 16 s are supplied with an ID letter for each group of 8 inputs to make them compatible with Honeywell Energy software The available choices are A B C D E F G H I J K L M N O P Q R S T U V W X and Y Z No other combinations are avail...

Page 5: ...plied with all modular jacks for use only with Honeywell E Mon meters Fig 1 Modular Jacks 2 Plug In Screw Type Connectors IDR 8 Supplied with all plug in screw type connectors for use with third party meters electric gas water etc that are provided with a dry contact pulse output Fig 2 Plug In Screw Type Connectors M33954 MODULAR JACKS M33955 SCREW TYPE CONNECTORS ...

Page 6: ...ne IDR configuration consists of a single IDR unit The enclosure should be mounted using the mounting flanges located at the top and bottom of the enclosure The enclosure has three available knockouts for cable entrance exit from the IDR NEVER ATTEMPT TO DRILL THROUGH THE STEEL ENCLOSURE DOING SO MAY PERMANENTLY DAMAGE THE ELECTRONIC CIRCUITRY AND WILL VOID ALL WARRANTIES Fig 3 JIC Steel Enclosure...

Page 7: ...erfaced with the IDR through the plug in screw type connectors Any of the connectors may be used with 22 14 AWG conductors 2 When used with solid state switches correct polarity must be observed in order for that contact to be rec ognized The left terminal of the screw terminal on the IDR must be connected to the plus side of the switch Fig 4 Meter Connections 3 The meter can be up to 500 feet awa...

Page 8: ... Indicators LCD backlite if the IDR is powered the LCD backlite is on 2 Meter LED Indicators There are three groups of LEDs located on the main power board Meter status BEAT STATUS and LOAD RS 485 communication TX and RX Ethernet communication ACT and LINK Table 1 LED Chart NOTE The AC adapter provides an isolated 9 VAC 300 mA power source for the IDR Contact Honeywell E Mon at 800 334 3666 if ano...

Page 9: ... up and down buttons are used to move the pointer The SELECT button allows entry to each of the functions Repeated use of this button allows the object selected to be modified The UP and DOWN buttons are used to modify the object that was selected Once changed the SELECT button is used to move to the next object to be modified When completed press the MENU button to save the setting and exit the f...

Page 10: ...E MON INTERVAL DATA RECORDER 62 0394 06 10 5 0 IDR DISPLAY CONTINUED 5 2 Normal Run Modes 1 Energy consumption kWh 2 Real Time Load kW ...

Page 11: ...dual IDRs NOTE The total combined cable length must be no more than 4 000 feet c Each IDR has two LEDs yellow and green located directly below the RS 485 jacks If the system is properly wired these two LEDs will normally be OFF These LEDs will flash when the computer and IDR are communicating Method 2 Terminal Block Method IDRs may also be daisy chained using a 3 conductor cable Instead of using t...

Page 12: ...and when lit indicates communication activity Communication protocol for the Ethernet IP port is selectable using the position 2 switch of S2 If position 2 is ON EZ7 is selected If position 2 is OFF Modbus TCP IP is selected IDR 2500s can be tied into a local Ethernet network Intranet or used on the Internet with a public IP Address Each device that is connected directly to the ethernet network re...

Page 13: ...lse Pulse Pulse Value R W 400231 410231 2 Usage Channel 12 Pulse Pulse Pulse Value R W 400251 410251 2 Usage Channel 13 Pulse Pulse Pulse Value R W 400271 410271 2 Usage Channel 14 Pulse Pulse Pulse Value R W 400291 410291 2 Usage Channel 15 Pulse Pulse Pulse Value R W 400311 410311 2 Usage Channel 16 Pulse Pulse Pulse Value R W 40065 41065 2 Demand Channel 1 Demand Demand Pulse Value R 40067 4106...

Page 14: ... 0000 0C Channel 0I Interval 0F 15 minute intervals 05 5 minute intervals 2 Each register represents a 15 or 5 minute pulse value based on the interval day block 96 registers max with 15 minute intervals 288 registers max with 5 minute intervals The first interval data register 44007 represents the pulse count for the first 15 or 5 minute interval beginning at midnight 3 The interval data headers ...

Page 15: ... Pulse Pulse Value Present Value R 151 Analog Input Usage Channel 15 Pulse Pulse Value Present Value R 161 Analog Input Usage Channel 16 Pulse Pulse Value Present Value R 17 Analog Input Demand Channel 1 Demand Pulse Value Present Value R 18 Analog Input Demand Channel 2 Demand Pulse Value Present Value R 19 Analog Input Demand Channel 3 Demand Pulse Value Present Value R 20 Analog Input Demand Ch...

Page 16: ...net Device ID Device Number of APDU retries R W With an IDR16 each channel 1 through 16 represents the IDR16 meter jack inputs 1 through 16 With an IDR8 each channel 1 through 8 represents the IDR8 meter jack inputs 1 through 8 Table 6 Honeywell E Mon LonWorks Point Map IDR8 and IDR16 Network Variable Name Function Block Index SNVT Type Description Units IDR nvoUsageCh011 1 SNVT_count_f Usage Chan...

Page 17: ...lse Value R nvoUsageCh281 28 SNVT_count_f Usage Channel 28 Pulse Pulse Value R nvoUsageCh291 29 SNVT_count_f Usage Channel 29 Pulse Pulse Value R nvoUsageCh301 30 SNVT_count_f Usage Channel 30 Pulse Pulse Value R nvoUsageCh311 31 SNVT_count_f Usage Channel 31 Pulse Pulse Value R nvoUsageCh321 32 SNVT_count_f Usage Channel 32 Pulse Pulse Value R nvoDemandCh01 33 SNVT_count_f Demand Channel 1 Demand...

Page 18: ... nvoDemandCh25 57 SNVT_count_f Demand Channel 25 Demand Pulse Value R nvoDemandCh26 58 SNVT_count_f Demand Channel 26 Demand Pulse Value R nvoDemandCh27 59 SNVT_count_f Demand Channel 27 Demand Pulse Value R nvoDemandCh28 60 SNVT_count_f Demand Channel 28 Demand Pulse Value R nvoDemandCh29 61 SNVT_count_f Demand Channel 29 Demand Pulse Value R nvoDemandCh30 62 SNVT_count_f Demand Channel 30 Demand...

Page 19: ...rror has occurred The interval data period window can be set to read 15 or 5 minutes using the nviIntDataPeriod This value will not change the default interval data period value of 15 minutes NviIntDataChan will select the usage channel For example set nviIntDataChan to 1 to read the interval data for nvoUsageCh01 4 NviRequest commands can disable or enable functional blocks Any changes will be sa...

Page 20: ...0 factory default 19 2k 38 4k and 76 8k bps higher baud rate would reduce cabling length When connecting the device to an RS 485 network needing the use of biasing the RS 485 line turn on DIP Switch pos 9 and pos 10 After changing the DIP switch selections 1 8 restart the device for the new settings to take effect 9 10 for BIAS doesn t require CPU restart Fig 8 DIP Switch Baud Rates Appendix B Cab...

Page 21: ...ocations Fig 10 LED Indicator Locations Appendix D IDR Circuit Board Components Fig 11 IDR Modular Jack M34077 CPU INDICATOR LEDS COMMUNICATION INDICATOR LEDS FOR ETHERNET COMMUNICATIONS M33958 BATTERY FOR RTC COMMUNICATION PORTS CPU RESET METER INPUTS EXTERNAL POWER IN ...

Page 22: ...LE TYPE CONNECTOR IDR TO METERS 1 8 6 COND 22 26 AWG RJ 45 PINS 1 8 NOT USED IDR TO IDR 4 COND 26 AWG RJ 11 IDR TO USB KEY 4 COND 26 AWG RJ 11 USB KEY TO COMPUTER 3 FT USB A to USB B Cable RJ 45 DTE IDR TO PULSE METER 2 COND 14 22 AWG SUPPLIED BY HONEYWELL NOTE INTERIOR INTERCONNECTING COMMUNICATIONS ARE SUPPLIED WITH THE PRE WIRED MMU TYPE METERING CABINETS NOTE WHEN CONSTRUCTING FIELD INSTALLED ...

Page 23: ...6 AWG RJ 45 PINS 1 8 NOT USED IDR TO USB KEY 4 COND 26 AWG RJ 11 IDR TO RS 232 KEY 2000 4 COND 26 AWG RJ 11 RS 232 KEY 2000 TO COMPUTER 8 COND 22 26 AWG RJ 45 DTE FLAT MODULAR CABLE IDR TO PULSE METER 2 COND 14 22 AWG SUPPLIED BY HONEYWELL NOTE INTERIOR INTERCONNECTING COMMUNICATIONS ARE SUPPLIED WITH THE PRE WIRED MMU TYPE METERING CABINETS NOTE WHEN CONSTRUCTING FIELD INSTALLED CABLES MODULAR CA...

Page 24: ...PER CHANNEL IDR A IDR A IDR Z UP TO 8 METERS UP TO 8 METERS UP TO 8 METERS IDR 8 USING HONEYWELL METERS CHANNEL 2 CHANNEL 1 UP TO 4000 FEET TOTAL AC ADAPTER UP TO 8 METERS CHANNEL 3 EKM T UP TO 4000 FEET TOTAL UP TO 4000 FEET TOTAL UP TO 4000 FEET TOTAL UP TO 26 IDR 16S PER CHANNEL PC PC IDR Z AC ADAPTER AC ADAPTER AC ADAPTER AC ADAPTER AC ADAPTER AC ADAPTER AC ADAPTER AC ADAPTER M37289 UP TO 8 ME...

Page 25: ...R METERS 1 16 USE 6 CONDUCTOR CABLE AC ADAPTER RS 232 KEY 6 FOOT CABLE PROVIDED BY HONEYWELL 15 FEET MAX RS 232 SERIAL PORT COM1 COM4 UP TO 16 METERS UP TO 16 METERS AC ADAPTER IDR IDR IDR IDR IDR IDR IDR IDR M37291 PC UP TO 4000 FEET TOTAL UP TO 4000 FEET TOTAL UP TO 26 IDR 16S PC 6 FOOT CABLE PROVIDED BY HONEYWELL 15 FEET MAX RS 232 SERIAL PORT COM1 COM4 RS 232 KEY UP TO 4000 FEET TOTAL UP TO 40...

Page 26: ...orts Max Pulse Input 600 pulses per minute 50 duty cycle Data Storage 36 days 5 minute sampling intervals 72 days 15 minute sampling intervals Interface with Honeywell E Mon submeters electric utility meters third party submeters gas meters water meters BTU meters and any meter equipped with a contact pulse output using available 2 screw terminals Power Consumption 2 watts maximum 1 2 watts typica...

Page 27: ...ormed with Honeywell E Mon s authorization and according to its approved procedures iii the alleged defect is a result of abuse misuse improper maintenance improper installation accident or the negligence of any party iv damaged as a result of events beyond Honeywell E Mon s control or other force majeure events or v used in conjunction with equipment components accessories parts or materials not ...

Page 28: ... M S Rev 06 18 Printed in United States By using this Honeywell literature you agree that Honeywell will have no liability for any damages arising out of your use or modification to the literature You will defend and indemnify Honeywell its affiliates and subsidiaries from and against any liability cost or damages including attorneys fees arising out of or resulting from any modification to the li...

Reviews: