background image

14

Maintenance and 
Troubleshooting

32-00055—01

This chapter is divided into two sections:

• Maintenance procedures
• Troubleshooting guide

Maintenance

Preventive maintenance is the key to a reliable, safe and
efficient system. The core of any preventive maintenance
system is a list of periodic tasks. The following are
suggestions for a monthly list and a yearly list.

NOTE

: The monthly list and yearly lists are an average

interval. If your environment is dirty, the intervals may be
shorter.

Monthly Checklist

1. Inspect flame-sensing devices for good condition and

cleanliness.

2. Check for proper inlet air/gas ratios.

3. Test all the alarm systems for proper signals.

4. Check ignition spark plugs and check proper gap.

5. Check valve motors and control valves for free, smooth

action and adjustment.

6. Check for proper operation of the ventilating

equipment.

7. Test the interlock sequence of all safety equipment;

manually make each interlock fail, noting that related
equipment closes or stops as specified by the
manufacturer.

8. Test flame monitoring control system by manually

shutting off gas to burner.

9. Test main fuel hand-valves for operation.

10.Clean or replace the combustion air blower filter.

Yearly Checklist

1. Test (leak test) safety shut-off valves for tightness of

closure.

2. Test air pressure switch settings by checking switch

movements against pressure settings and comparing
with actual impulse pressure.

3. Visually check ignition cable and connectors.

4. Inspect impulse piping for leaks.

5. Clean and inspect all the burners.

6. Remove and clean the orifice plates 

.

7. Make sure that the following components are not

damaged or distorted:

• burner nozzle
• spark plugs
• flame sensors
• flame tube or combustion block

5

Summary of Contents for Eclipse ImmersoPak IP004

Page 1: ...Eclipse ImmersoPak Burners Model IP004 012 Version 3 Operating Instructions Edition 9 16 32 00055 01 ...

Page 2: ...nt parts and Honeywell Eclipse will not be liable for any other injury loss damage or expenses whether direct or consequential including but not limited to loss of use income or damage to material arising in connection with the sale installation use of inability to use or the repair or replacement of Honeywell Eclipse s products Any operation expressly prohibited in this manual any adjustment or a...

Page 3: ...efore Installation 7 Burner Installation 7 Flame Sensor Installation 8 Checklist After Installation 8 Adjustment Start Stop 10 Step 1 Reset the System 10 Step 2 Verify the Air Flow 11 Step 3 Set Low Fire Air 11 Step 4 Ignite the Burner 11 Step 5 Verify the Settings 13 Maintenance Troubleshooting 15 Maintenance 15 Monthly Checklist 15 Yearly Checklist 15 Troubleshooting Procedures 16 Appendix i Con...

Page 4: ...udience This manual has been written for people who are already familiar with all aspects of a nozzle mix burner and its add on components also referred to as the burner system These aspects are Installation Use Maintenance The audience is expected to have previous experience with this type of equipment ImmersoPak Documents Installation Guide No 360 This document Datasheet Series No 360 Available ...

Page 5: ...reated by sanding sawing grinding cutting and other construction activities could release crystalline silica Crystalline silica is known to cause cancer and health risks from the exposure to these chemicals vary depending on the frequency and length of exposure to these chemicals To reduce the risk limit exposure to these chemicals work in a well ventilated area and wear approved personal protecti...

Page 6: ...sting marks from UL FM CSA European EN 746 2 with CE mark from TuV Gastec Advantica Electrical Wiring All the electrical wiring must comply with all applicable local codes and or standards such as NFPA Standard 70 ANSI C11981 EN 746 2 Gas Piping All the gas piping must comply with all applicable local codes and or standards such as NFPA Standard 54 ANSI Z223 EN 746 2 Where to Get the Standards The...

Page 7: ...For bolt hole patterns see the datasheet for your ImmersoPak model If adapters are used burner flange should not be spaced further than 4 from tank wall Figure 3 1 Bolt Hole Pattern Tank wall Make sure that the wall of the tank is strong enough to carry the weight of the burner If necessary reinforce the tank wall area where you plan to install the burner Burner Piping The burner is factory assemb...

Page 8: ...tall and connect a UV scanner refer to scanner information guide Flame Rod If the flame rod option was selected when the burner was ordered the burner will be delivered with the flame rod already installed on the burner NOTE Only specific burner sizes are capable of using a flame rod These models are IP004 005 and 006 For detailed information on how to install and connect a flame rod refer to Bull...

Page 9: ... and other limit interlocks Be sure the switches fail as intended in the event of a power failure If simulated limits or simulated flame failures do not shut down the fuel system within the required failure response time immediately correct the problem before proceeding 8 Adjust main gas inlet pressure to the ratio regulator within the range specified in the appropriate datasheet Gas inlet pressur...

Page 10: ...Drive control motor to low fire position 3 Set low fire air a Loosen the set screw on burner side of coupling NOTE There is a slot in the end of the BV shaft that is parallel to the air damper This slot is used for visual indication of the BV position The BV is closed when the shaft slot is perpendicular to the direction of air flow through the BV Figure 4 4 Air BV Shaft b Rotate air BV shaft to f...

Page 11: ...just the control motor to incrementally increase gas flow c Attempt to ignite burner d Repeat steps b and c until burner ignites If necessary refer to Chapter 5 for troubleshooting tips 8 Flame signal strength Adjust gas flow as described above in step 7b to maintain a stable flame signal and reliable ignition NOTE If viewing the flame it should be blue with flashes of yellow When firing propane o...

Page 12: ...flame signal and reliable ignition NOTE If viewing the flame it should be blue with flashes of yellow When firing propane or butane a proper low fire flame may have sustained flashes of yellow 9 Verify low fire flame if applicable a Shut off gas Allow process to cool b Verify repeatability of ignition and low fire flame signal at cold conditions 10 Shut down the system Figure 4 8 Step 5 Verify Set...

Page 13: ... burner if the settings do not repeat as expected If necessary refer to Chapter 5 Maintenance Troubleshooting 8 Record all setup data as an aid for future troubleshooting and setup operations Do not turn the combustion air blower off immediately Allow time for the process to cool This will prevent hot gases from back flowing into the burner and blower causing damage to the burner 9 Stop the burner...

Page 14: ... free smooth action and adjustment 6 Check for proper operation of the ventilating equipment 7 Test the interlock sequence of all safety equipment manually make each interlock fail noting that related equipment closes or stops as specified by the manufacturer 8 Test flame monitoring control system by manually shutting off gas to burner 9 Test main fuel hand valves for operation 10 Clean or replace...

Page 15: ...r No ignition open circuit between the ignition transformer and the igniter Repair or replace the wiring to the igniter No ignition the igniter needs cleaning Clean the igniter No ignition the igniter is not correctly grounded to the burner Clean the threads on the igniter and the burner NOTE Do not apply grease to the threads on the igniter No ignition igniter insulator is broken Igniter is groun...

Page 16: ...the low fire air butterfly valve position The burner goes out when it cycles to high fire Not enough gas pressure into the ratio regulator Check the start up settings Measure the gas pressures and adjust them where necessary Check for valve train pressure loss Loading line to the ratio regulator is leaking Repair the leak in the loading line The burner is erratic and does not respond to adjustment...

Page 17: ...ration Low gas pressure switch has activated Check incoming gas pressure Adjust gas pressure if necessary Check pressure switch setting and operation Malfunction of the flame safeguard system e g shorted out flame sensor or electrical noise in the sensor line Have a qualified electrician troubleshoot and correct the problem No power to the control unit Have a qualified electrician troubleshoot and...

Page 18: ... x 10 3 millimeter mm inch in 3 94 x 10 2 MJ Nm Btu ft standard 26 86 From To Multiply By kiloPascals kPa millibar mbar 10 meter m millimeter mm 1000 millibar mbar kiloPascals kPa 0 1 millimeter mm meter m 0 001 From To Multiply By actual cubic foot h acfh actual cubic meter h am h 2 832 x 10 2 standard cubic foot h scfh normal cubic meter h Nm h 2 629 x 10 2 degrees Fahrenheit F degrees Celsius C...

Page 19: ...Notes 32 00055 01 19 ...

Page 20: ...ntrol Solutions Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 customer honeywell com U S Registered Trademark 2016 Honeywell International Inc 32 00055 01 M S 09 16 Printed in United States ...

Reviews: