Cannot initiate a start
sequence.
Air pressure switch has not made contact. Check air pressure switch adjustment.
Check air filter.
Check blower rotation.
Check outlet pressure from blower.
High gas pressure switch has
activated.
Check incoming gas pressure.
Adjust gas pressure if necessary.
Check pressure switch setting and
operation.
Low gas pressure switch has activated.
Check incoming gas pressure.
Adjust gas pressure if necessary.
Check pressure switch setting and
operation.
Malfunction of the flame safeguard system
(e.g., shorted-out flame sensor or electrical
noise in the sensor line).
Have a qualified electrician troubleshoot
and correct the problem.
No power to the control unit.
Have a qualified electrician troubleshoot
and correct the problem.
Main power is off.
Be sure the main power to the system is
switched to the “on” position.
Problem
Possible Cause
Solution