2. Installation
2.2. Condensed Specifications
Revision 2.0
EDC201 / EDC202 / EDC203 Product Manual
7
July 2015
2.2 Condensed
Specifications
Honeywell recommends that you review and adhere to the operating limits listed in Table 2-1:
Condensed Specifications, Table 2-2: TC/RTD Types and Scope, and Table 2-3: Environmental and
Operating Conditions when operating your controller.
Specifications
Inputs
Input Type
TC: E, J,K,Platinel II,Ni-Ni-Moly,R,S,T
RTD: PT100,PT100(Low)
Input Sampling Time
TC
:
250ms
RTD
:
350ms
Control
Relay output
Dry contact /NO
5A@ 30 VDC or 250 VAC
SSR Driver Output
24VDC/20 mA
Algorithm ON-OFF
Time proportioning
TPSC
Alarm Outputs
Dry
contact/NO
5A@ 30 VDC or 250 VAC
Mode PROCESS
VARIABLE
DEVIATION
OUTPUT
CONTROL MODEALARM
PV RATE OF CHANGE
DIGITAL INPUT
THERMOCOUPLE WARNING
THERMOCOUPLE FAILING
FAILSAFE
SYSTEM DIAGNOSTIC
TIMER ALARM
LED
PV/SP indicator
4-digit, 7-segment display
Indication accuracy
0.5%
Alarm relay status
Alarm1 or Alarm2