3. Configuration
3.4. Input Set Up Group
22
EDC201 / EDC202 / EDC203 Product Manual
Revision 2.0
July 2015
Set up
Group
Function
Prompt
7-Segment
Code
Default
Value
Selection or
Range of
Setting
7-Segment
Code
Parameter
Definition
Top Display
Upper Display
Lower Display
UP
UP
UPSCALE
BURNOUT will force
the Input signal to
the full scale value
when the sensor
fails.
The maximum
permissible PV value
shall be:
The maximum value
= Ratio *(High Range
+ 1% of range span)
+ Bias;
Which shall not be
greater than (High
Range + 10% of
range span)
DOWN
DOWN
DOWNSCALE
BURNOUT will force
the Input signal to
the lower range
value when the
sensor fails.
The minimum
permissible PV value
shall be:
The minimum value
= Ratio*(Low Range
– 1% of range span)
+ Bias;
Which shall not be
less than (Low
Range – 10% of
range span)
NO FS
NO FS
No configured
Failsafe output
applied if failed input
is detected. This
selection provides
input failure detection
and alarm.