Enhanced Micro TDC 3000 User’s Manual
6-2
9/95
6.1
The Enhanced Micro TDC 3000 towers contain an air filter located just above the
Multinode Module. Figure 6-1 shows the location of the scotfoam air filter. Subsection
6.3 contains information on how to gain access to the air filter.
53322
Scotfoam
Air Filters
Figure 6-1 — Location of Air Filter in Tower #1 and #2
Table 6-1 gives a summary of a recommended inspection schedule for different operating
environments. Maintenance is performed by removing, cleaning (by hand-washing) and
reinstalling the air filter. If the air filter has been cleaned numerous times, total replacement
may be necessary. It can be ordered through logistics using part number 51201201-600.
Table 6-1 — Recommended Periodic Inspection and Cleaning of Air Filters
Equipment Operating
Environment
Frequency of Inspection
and Cleaning
Harsh
30 Days
Heavy
60 Days
Moderate
90 Days
Office
6 Months