Enhanced Micro TDC 3000 User’s Manual
5-7
9/95
5.2.2
5.2.2 Loading Network Interface Module and UCN Devices
The Network Interface Module is loaded through the Gateways and Interfaces Status
display, which is called up by selecting
GATEWAYS
on the System Status display.
1. Select the node number 3 (primary) or 4 (redundant) for the NIM to be loaded.
2. If the
AUTOLOAD NET
target is present, select
AUTOLOAD NET,
press
ENTER
,
and skip to step 4. Otherwise, select
MANUAL
LOAD
. Continue with step 3.
3. Select
OPERATOR
PROGRAM
, and follow the prompters to specify the program
source [normally, you will select the default source (NET = HM)]. Then, select
EXECUTE
COMMAND
.
4. Wait from a few seconds to a few minutes for the status for the NIM you selected in
step 1 to go to
OK.
UCN CONTROL STATE: BASIC
UCN AUTO CHECKPNT: INHIBIT
NIM AUTO CHECKPNT: DISABLE
53290
UCN 10 STATUS
UCN CABLE STATUS: OK
MAKE SELECTION
24 Feb 15:50:06 1
LOAD/SAVE
RESTORE
PROGRAM
LOAD
CONTROL
STATES
RESTORE
DATA
AUTO
CHECKPT
UCN CABLE
STATUS
SAVE
DATA
RUN
STATES
DETAIL
STATUS
LADDER
LOAD
LADDER
SAVE
SLOT
SUMMARY
ENTER
CANCEL
01 NIM 02
OK
BACKUP
03 PM 04
OK
BACKUP
05 PM 06
ALIVE
ALIVE
07 LM 08
OK
BACKUP
When the NIM is loaded and operating (primary NIM status =
OK
), you can load the APM
program and restore Advanced Process Manager data through the UCN status display.
Refer to subsection 4.4 in this manual.
Summary of Contents for Enhanced Micro TDC 3000
Page 1: ...L 8 Node Enhanced Micro TDC 3000 User s Manual MT11 520 ...
Page 2: ......
Page 10: ...Enhanced Micro TDC 3000 User s Manual iv 9 95 ...
Page 56: ...Enhanced Micro TDC 3000 User s Manual 3 8 9 95 ...
Page 82: ...Enhanced Micro TDC 3000 User s Manual 4 26 9 95 ...
Page 128: ...Enhanced Micro TDC 3000 User s Manual 5 46 9 95 ...
Page 144: ...Enhanced Micro TDC 3000 User s Manual 6 16 9 95 ...
Page 156: ...Enhanced Micro TDC 3000 User s Manual B 4 9 95 ...
Page 168: ...Enhanced Micro TDC 3000 User s Manual Index 12 7 95 ...
Page 171: ......