Metering Lines (4)
6 - 9
Model 1010 Application Pack CB
Part No.: 4418024 - Rev. 1
Programming Manual
Meter n
4 mA Pressure
The pressure that corresponds to a 4 mA reading from the pressure
transmitter for the meter.
Constraints:
Only available when you use the Weights and Measures switch on
the instrument to enter programming mode.
Available only if pressure correction is enabled.
Enter a value in the following range:
Meter n
20 mA Pressure
The pressure that corresponds to a 20 mA reading from the Pressure
Transmitter for the Meter.
Constraints:
Only available when you use the Weights and Measures switch on
the instrument to enter programming mode.
Available only if pressure correction is enabled.
Enter a value in the following range (Whichever of the following options
is lesser):
4 mA setting to 4 mA s 1000 kPa (for METRIC units)
4 mA setting to 4 mA s 145 psi (for US units)
Or
4 mA setting to Max range in Table 6-3
Breakdown Pressure
Allows enabling or disabling the breakdown pressure.
Constraints:
Only available when you use the Weights and Measures switch on
the instrument to enter programming mode.
Available only if pressure correction is enabled.
Select one of the following options:
Enable
Disable*
Meter n
Breakdown Pressure
Allows entering of the breakdown pressure. This value is used for
correction calculations if the pressure probe fails.
Table 6-3: Commodity Based Density Range
Units
Base
Temp
Crude
Oils
(A)
Refined
(B)
Special
(C -
thermal
exp.)
Lube Oils
(D)
NGL and LPG
(E)
FAME
(F)
PSI
60 °F
0 to 1500
N/A
0 to 1500
100 to 2200
N/A
kPa
15 °C
0 to 10340
N/A
0 to 10340
689.48 to 15168.47
N/A
20 °C