NFS Supra
Page 13
HLS-MN-025 v.04
Installation and Operating Manual
www.honeywelllifesafety.es
www.hoeywelllifesafety.es
Sounders delayed
(yellow):
This led indicates that the sounders are programmed with delays for detector alarms in a zone.
-Led On: There are delays configured for sounders.
-Led flashing: Delays operating. When delays are finished, sounders are activated. Press the
Delay On/Off
key to stop the
operating delays. Sounders are activated immediately when there is an alarm in the system.
Power Supply Fault (
Yellow):
This led indicates that there is a fault in the control panel power supply.
-Led On: Power supply fault. Check the 220 Vac power supply and batteries, the fuses of both and the Aux. 24V output. When the
fault cause has been cleared, press the
Reset
key (Access level
2) to make the system return to its normal state.
Auxiliary Power Supply Fault
(Yellow):
This led indicates that there is a fault in the Auxiliary 24V output.
-Led On: Auxiliary Power Supply Fault. Check the 24V AUX fuses.
When the fault cause has been cleared, press the
Reset
key
(Access level 2) to make the system return to its normal state.
Note: This fault can cause, field device malfunction if they are powered by this output.
System Fault
(yellow):
A serious system fault has been detected.
-Led On: System fault. Switch off the 220V power supply and batteries until the Power led is off and connect the power supply
again. If the fault continues, contact your supplier.
Note: In case that the external relays or communication boards are installed but not communicating with the NFS supra control
panel, the system fault led will light.
Operation