NFS Supra
Page 16
HLS-MN-025 v.04
Installation and Operating Manual
www.honeywelllifesafety.es
www.hoeywelllifesafety.es
SILENCE/RESOUND
:
It allows to Silence/Resound and disable sounders.
-Silence/Resound:
Press the
Silence/Resound
key to silence the sounders, the Silence/Resound led will be lit. Press this key
again to activate sounders again
.
-Disable sounders: When no alarms are activated, press the
Silence/Resound
key once to disable sounders, the Disablement
and Sounders fault/disabled leds will be lit. Press the Sounders Stop key again to activate the sounders. The disabled sounders
will not be activated in case of alarm
.
EVACUATE:
By pressing this key all sounders will be activated in order to evacuate the building.
-Evacuate: Press this key to activate all sounders.
To silence sounders press the
Silence/Resound key
.
DELAY ON/OFF
:
If there are delays configured for sounders, the
Sounders Delayed
led will light, the general Disablement led will
light to indicate the sounders are delayed. Press the
Delay On/Off
key, then the
Delay On/Off
led will be illuminated with the
delays disabled. While delays are operating, press the
Delay On/Off
key
in order to disable the delays and activate the sounders immediately.
RESET:
Press this key to reset the system. Any existing alarm or fault will be indicated again after resetting the system
Check the alarm or fault cause before resetting the system
ZONE KEYS
:
-
To disable a zone:
Press the zone key once. The Disablement and Zone keys leds will be lit. If a zone is already disabled, no
alarms or faults will be received.
If a zone with an event is disabled, this zone will be disabled for new events but the current alarm or faults will only disappear after
a system reset.
-
To test a zone:
press a zone key from the previous disablement status. The test and zone key leds will flash to indicate the test
status.
The alarms in zones being tested will activate all the sounders for a few seconds and the zone is reset automatically. While zones
are tested, the fault relay changes its status to indicate the new condition.
The alarm of any zone in normal status, not under test, will disable the test mode and activate the system normal operation.
Operation