NFS Supra
Page 18
HLS-MN-025 v.04
Installation and Operating Manual
www.honeywelllifesafety.es
www.hoeywelllifesafety.es
3.4 Installation Procedure
Installation of the NFS Supra control panel, in line with
concept,
is comprised of two stages: mounting plate installation and panel enclosure
installation. Details of each stage are provided in the following sections.
3.4.1 Mounting Plate Installation
To prevent distortion, the NFS Supra mounting bracket MUST be installed
on the wall as flat as possible, i.e. with a maximum flatness deviation
between any two points of 3mm. Where the wall is out of tolerance, use
appropriate packing pieces to meet these requirements.
Step 1:
• Hold the mounting plate in the required position on the wall and mark
the position of the 3 fixing holes. Use a level to ensure these are level.
• Remove the mounting plate from the wall and drill the 3 holes.
• Use rawlplugs or equivalent (Ø 6mm) to the 3 holes.
Step 2:
• Screw the mounting plate to the wall, using the top fixing hole only at
this stage and appropriately sized screws.
Step 3:
• Line the 2 holes in the lower area of the mounting plate with the two
holes in the wall drilled earlier. Use suitably sized screws to secure
the mounting plate to the wall.
Step 4:
• Remove all blanks from the 20mm cable-entry apertures required for
all cable access.
Installation