NFS Supra
Page 34
HLS-MN-025 v.04
Installation and Operating Manual
www.honeywelllifesafety.es
www.hoeywelllifesafety.es
5 Configuration
5.1 Introduction
It´s possible to configure output and control functions from Access Level 3.
Before changing the panel configuration, read this section carefully. Do not make any changes
in the configuration unless you have completely understood the operation of the panel.
The default configuration is valid for most installations and does not need to be modified.
Please observe that some configurable functions available may contravene local applicable
regulations.
5.2 Level 3 Access (configuration)
Inside Level 3, the system leds and push-buttons have special functions. Check each
option to know its meaning and usage.
Configuration access (PROG)
In order to enter the configuration menu, connect the supplied jumper between the PROG
connector pins on the main board.
The buzzer will sound briefly every
10 seconds to
indicate the access to level 3. The
fault relay will remain activated while the panel is in
level 3.
The system leds indicate the configuration of the first option (Digital input).
Follow the steps of each option to modify their values.
Exit configuration
Once the configuration is finished, remove the jumper from the PROG connector on the main
board and the configuration will be saved in the inner memory.
Configuration
PROG. Jumper
Level 3 Access Jumper
10 s.