NFS Supra
Page 36
HLS-MN-025 v.04
Installation and Operating Manual
www.honeywelllifesafety.es
www.hoeywelllifesafety.es
5.4 Configuration Options
In NFS Supra control panels, the following functions can be configured:
At level 3, the panel leds indicate, the configuration for each option. In order to select one
option, the relevant push button must be pressed, following the lighted keys. System leds
(Inferior group of leds from 1 to 10) indicate the selected configuration.
In order to change a function, press
RESET
. Select the led corresponding to the desired option
in each menu. On removing the level 3 access jumper (PROG), the control panel saves the
configuration automatically.
When entering the configuration, you will always Access at the option 1 (Digital Input).
5.4.1 Zone type
Zone operation may be configured as follows:
Normal
operation (by default)
: Zone alarms are activated immediately.
Delayed contact (470
)
: To be used with flow switches or contacts with
470
alarm resistor that require that the alarm condition remain for 30 seconds before the
control panel
indicates an alarm. Call points activate the alarm immediately.
Verification (Detectors)
:
This option requires a second acknowledge/confirmation within 10 minutes or the activation of the same or any other zone. After the first
alarm, the zone is reset and the alarm is confirmed if a new alarm occurs in the next 10 minutes.
Delayed contact (470
and Zener 5V)
. Both alarm contacts
470
alarm resistor and call points must keep the alarm condition for 30 seconds, otherwise the
alarm will not be indicated.
Reset push button:
Change Option
(Access Level 3 - Configuration)
Configuration
1
2
3
4
5
6
7
8
9
10
Configuration Option indication
from 1 to 10.