Zone type configuration:
Select the desired zone by pressing the relevant push-button
ZONE
=ON (Red or Yellow)
. The
zone led will be lit in red or yellow, depending on the short also section fault/alarm by short
circuit.
Zone Short Circuit Configuration by pressing the zone key:
Zone = ON (Yellow) = Short circuit is fault
Zone = ON (Red) = Short circuit is alarm
Change zone type cyclically by pressing
RESET.
Zone Configuration
Led 1 Alarm Red
= ON =
Normal
(By default)
Led 2 Disablement Yellow
=ON=
Delay contact
30s. (470
).
Zener immediate activation
Led 3 Test yellow
=ON=
Verification
. 10 minutes.
Led 4 Power green
=ON=
Delay contact
30 sec. (470
and Zener)
Reset push-button:
Change Option
(Access Level 3 configuration)
The sounder and relay cards outputs operation depends on the zone configuration
associated with these outputs.
Configuration
Note: The zone led will be lit in red or yellow,
depending on the short circuit option configuration
for zones alarm or fault