NFS Supra
Page 5
HLS-MN-025 v.04
Installation and Operating Manual
www.honeywelllifesafety.es
www.hoeywelllifesafety.es
1.4 General
The NFS Supra control panel has been designed to manage correctly and according to, UNE-EN 54-2 and UNE-EN 54-4/A2:2006 fire alarm control systems.
The control Panel can support an unlimited number of manual call points and a limited number of detectors by zone, according to the limits of design and
installation standards that are applicable. Some approvals, certifications and proper functioning of the system, is ensured by the use and recommendations set by
the manufacturer of fire detectors, optical acoustic alarm indicators and peripheral equipment connected to this fire alarm control panel. Read the reviews and
features defined in this manual as well as any of the equipment to be connected to the panel, to ensure proper compatibility
The operational performance of the panel is microprocessor-controlled and has several configuration options, in addition to the mandatory requirements of sounder
delays, zone monitoring or test mode. Check the system settings (or default configuration) before making any Test.
1.5 Warnings and Cautions
Installation:
This Control Panel design is based on a modular build concept
, which offers the user completely flexible system solutions. The electronic
components are part of a separate module, which need not be installed until system commissioning is to be undertaken.
Before installing this control panel, please thoroughly read and understand the installation section of this manual and installation instructions or
manuals of every each device
, which provide detailed information on mounting, wiring, and installing the system.
This panel or devices connected to it can be damaged if you do not follow the instructions described in this manual
. Do not connect or disconnect any
device without disconnecting all power sources as they can result in serious damage.
Commissioning:
To install and configure the NFS Supra control panel, carefully follow the steps in this manual. It is recommended by manufacturer to check the
wiring lines before making any connection to the panel or field devices.
The NFS Supra control panel includes integrated power supply and space provision for two sealed, lead-acid gel standby batteries. In accordance with UNE-EN
54-4: A2: 2006, mandatory standard from August 2009, it is necessary to supervise the internal battery resistance to guarantee the battery correct operation in the
event of a power supply fault. The control panel carries regular readings of internal battery resistance to check the resistive value.
If this val
ue exceeds 700 mΩ,
the control panel will show a power supply fault,
indicating that the battery status is not correct
The lead-acid gel battery deep discharge and the use of low-quality batteries with high internal resistance can cause damage and malfunction of the system.
Although the control panel allows a wide margin in the supervision and types of batteries,
DO NOT INSTALL discharged batteries
or
those with which the
system indicates fault
. Consult the manufacturer for recommended battery types and models.
Note:
While every effort is made to ensure the accuracy of the content of this manual, the manufacturer reserves the right to change the information without notice.
Introduction