43.5mm sq
50mm sq
6.5 mm
32.5 mm
26 mm
Polarity-free
digital output.
Connection to
ballast only.
Do not connect
to other detectors.
Red - Live
Blue - Neutral
Yellow
Green
750mm
lead
Electrical Connections
Only suitably qualified personnel should install this equipment.
Mounting Details
CL
Cable entry point
14
.5m
m
CL
14.5
mm
20
.3m
m
Mid-Bay & Hi-Bay LightSpot Luminaire Controllers
Installation
Snap-in to infill panel (max 0.7mm/ 22 SWG) or use any combination of fixing holes on rear. Use only No 4
type B
º
inch self-tapping screws. Ensure that projection of screws into pilot holes does not exceed 4.5mm.
The recommended position for the detector is in the middle of the luminaire. Where this is not possible and the
detector is fitted near one end of the lamps, please ensure that the detector is at the ‘cold’ end of the lamps.
In order to achieve satisfactory light-level regulating operation, a detector must observe a substantially greater
proportion of artificial light from the luminaire(s) under its control than from neighbouring luminaires not under its
control. This is particularly important when planning the installed layout of linear luminaires that have an
integral detector positioned at one end.
To Test Luminaire Controller Operation
Once the Luminaire Controllers have been installed within the luminaires, the HC5, HC6 or HP18 may be used
to switch luminaires ON and OFF. Luminaires with regulating ballasts will also dim and brighten.