Commissioning with HP2000
(HP10 or HP18 can also be used but do not give access to the full range of features)
It is important that the HP2000 be held perpendicular and at a distance of between 0.5m and 2m from the detector.
1. Switch on HP2000 by pressing the red power button.
2. Point HP2000 at detector and press the DOWNLOAD button. The HP2000 will confirm the product’s identity,
and call up the correct menu of parameters and their current settings. It will also show the ballast type and the
duration (shown in hours) remaining on the 100-hour burn-in.
3. Use a combination of UP, DOWN, FORWARD and BACK buttons to navigate the parameter menu, selecting
options for each shown. (See Tips below.)
4. When options for all parameters have been selected, point the HP2000 at the detector and press the UPLOAD
button. The luminaire(s) will switch off briefly during the programming process and the HP2000 shows DATA
OK to confirm operation.
5. After a short period of inactivity (default 5 minutes), the HP2000 hibernates retaining the most recent settings.
Tips
i) Where there are only two options such as ON/OFF, a double click of the OK button toggles between them.
ii) Where there are multiple options, a double click of the OK button recalls a list of all options for that parameter.
Use the UP, DOWN and OK buttons to select.
iii) Use the OK button to go forward (through the menus) without displaying help pages.
iv) Press UPLOAD at any time to transfer all current settings from the handset to the product.
Please refer to HP2000 instructions for comprehensive commissioning details.
Factory Default Settings
These are the settings to which the units have been programmed before they leave the factory:
W5099B
Parameter
Options
Default
Power Up
On / Off
On
Response
Auto / Semi-Auto
Auto
1 min - 96 hrs, 10-sec (walk-test), Disabled (via HP2000)
5-35 mins (in 5 minute increments), walk-test (via HP10)
5, 10 or 20 mins, walk-test (via HP18)
On Sensitivity
0-100
100
Start Lamps
Max / Min
Max
Entry Scene
1-6
1
Bright Out
Yes / No
No
Dimming
Reg 50%-Reg100%
Reg 100%
Lamp Max
10%-100%
1
Fade to Off
Yes / No
No
When Vacant
10 Exit Scenes
Off
Set-Point High
0-1023
1023
Set-Point Low
0-1023
1023
100 Hour Burn-In
See Application Note: AN4028
0 hr
Additional feature accessible under Utilities:
Off Delay
20 mins