Commissioning with HP2000 

(HP10 or HP18 can also be used but do not give access to the full range of features) 

It is important that the HP2000 be held perpendicular and at a distance of between 0.5m and 2m from the detector.   
1. Switch on HP2000 by pressing the red power button.
2.   Point HP2000 at detector and press the DOWNLOAD button.  The HP2000 will confirm the product’s identity, 

and call up the correct menu of parameters and their current settings. It will also show the ballast type and the 

duration (shown in hours) remaining on the 100-hour burn-in.

3. Use a combination of UP, DOWN, FORWARD and BACK buttons to navigate the parameter menu, selecting 

options for each shown. (See Tips below.) 

4. When options for all parameters have been selected, point the HP2000 at the detector and press the UPLOAD 

button.  The luminaire(s) will switch off briefly during the programming process and the HP2000 shows DATA 

OK to confirm operation.

5. After a short period of inactivity (default 5 minutes), the HP2000 hibernates retaining the most recent settings.

Tips

i)  Where there are only two options such as ON/OFF, a double click of the OK button toggles between them. 
ii)   Where there are multiple options, a double click of the OK button recalls a list of all options for that parameter.  

Use the UP, DOWN and OK buttons to select.

iii)  Use the OK button to go forward (through the menus) without displaying help pages.
iv)   Press UPLOAD at any time to transfer all current settings from the handset to the product.

Please refer to HP2000 instructions for comprehensive commissioning details.

Factory Default Settings

These are the settings to which the units have been programmed before they leave the factory:

W5099B

Parameter

Options

Default

Power Up

On / Off

On

Response

Auto / Semi-Auto

Auto 

1 min - 96 hrs, 10-sec (walk-test), Disabled  (via HP2000)
5-35 mins (in 5 minute increments), walk-test (via HP10)
5, 10 or 20 mins, walk-test (via HP18)

On Sensitivity

0-100

100

Start Lamps

Max / Min

Max

Entry Scene

1-6

1

Bright Out

Yes / No

No

Dimming

Reg 50%-Reg100%

Reg 100%

Lamp Max

10%-100%

1

Fade to Off

Yes / No

No

When Vacant

10 Exit Scenes

Off

Set-Point High

0-1023

1023

Set-Point Low

0-1023

1023

100 Hour Burn-In

See Application Note: AN4028

0 hr

Additional feature accessible under Utilities:

Off Delay 

20 mins

Summary of Contents for Ex-Or Mid-Bay MS1200DIMBW

Page 1: ...asts MS1200DALIHBW for DALI ballasts Mid Bay Hi Bay LightSpot Luminaire Controllers Note HP2000 or HP10 HP18 required for commissioning HC5 HC6 or HP18 required for user override Please note that the HP10 and HP18 offer different limited programming options Installation and Commissioning Instructions ...

Page 2: ...osition for the detector is in the middle of the luminaire Where this is not possible and the detector is fitted near one end of the lamps please ensure that the detector is at the cold end of the lamps In order to achieve satisfactory light level regulating operation a detector must observe a substantially greater proportion of artificial light from the luminaire s under its control than from nei...

Page 3: ...t settings Tips i Where there are only two options such as ON OFF a double click of the OK button toggles between them ii Where there are multiple options a double click of the OK button recalls a list of all options for that parameter Use the UP DOWN and OK buttons to select iii Use the OK button to go forward through the menus without displaying help pages iv Press UPLOAD at any time to transfer...

Page 4: ...x meter on the working plane to remain constant when daylight illuminates the ceiling and the working plane to a differing extent Therefore products of this type should be regarded as capable of maintaining anAPPROXIMATE light level only 6 In order to achieve satisfactory light level regulating operation a detector must observe a substantially greater portion of artificial light from the luminaire...

Reviews: