Red  -  Live     

Blue  -  Neutral

Yellow 

Green

 

White -  MLS Bus +ve

Black  -  MLS Bus -ve

Electrical Connections

Polarity-free 

digital output

Connection to ballast only.

Do not connect to other detectors.

750mm

lead

26mm

32.5mm

6.5mm

43.5mm sq

50mm sq

Only suitably qualified personnel should install this equipment.

Installation

 

Snap-in to infill panel (max 0.7mm/ 22 SWG) or use any combination of fixing holes on rear.  Use only No 4 

type B 

º

 inch self-tapping screws.  Ensure that projection of screws into pilot holes does not exceed 4.5mm.

The recommended position for the detector is in the middle of the luminaire.  Where this is not possible and the 

detector is fitted near one end of the lamps, please ensure that the detector is at the ‘cold’ end of the lamps.

In order to achieve satisfactory light-level regulating operation, a detector must observe a substantially greater 

proportion of artificial light from the luminaire(s) under its control than from neighbouring luminaires not under its 

control.  This  is particularly important when planning the installed layout of linear luminaires that have an 

integral detector positioned at one end.

To Test with HC5 or HC6

Once the MLS Digital Luminaire Controllers have been installed within the luminaires, the HC5 or HC6 may be 

used to switch luminaires ON and OFF.  Luminaires with regulating ballasts will also dim and brighten.

Mounting Details 

CL

Cable entry point

14

.5m

m

CL

14.5

mm

20

.3m

m

MLS Digital Luminaire Controllers: MLS2000DIS / MLS2000DIW for DSI ballasts

MLS2000DALIS / MLS2000DALIW for DALI ballasts

Summary of Contents for Ex-Or MLS

Page 1: ...d Commissioning Instructions Note HP2000 required for commissioning HC5 or HC6 required for testing MLS Digital Luminaire Controllers MLS2000DIS MLS2000DIW for DSI ballasts MLS2000DALIS MLS2000DALIW for DALI ballasts ...

Page 2: ...mps please ensure that the detector is at the cold end of the lamps In order to achieve satisfactory light level regulating operation a detector must observe a substantially greater proportion of artificial light from the luminaire s under its control than from neighbouring luminaires not under its control This is particularly important when planning the installed layout of linear luminaires that ...

Page 3: ...the OK button toggles between them ii Where there are multiple options a double click of the OK button recalls a list of all options for that parameter Use the UP DOWN and OK buttons to select iii Use the OK button to go forward through the menus without displaying help pages iv Press UPLOAD at any time to transfer all current settings from the handset to the product Please refer to HP2000 instruc...

Page 4: ...rs 4 This equipment should be used to control only those ballasts powered from the same phase as the detector 5 Do not connect mains to the MLS bus 2 6 It is imperative that the MLS bus is wired with the correct type of cable normally it should be 1 5mm unscreened twisted pair Please readApplication NoteAN4001 for more details 7 Due to the fact that the photocell is on the ceiling looking down it ...

Reviews: