background image

W4087G

Technical Data

 

 

MLS CA

MOUNTING HEIGHT: 3.0m max

RANGE:  Cone-shaped detection pattern, diameter (at floor level) = 2.4 x mounting height

OPERATING VOLTAGE: 230V 50Hz (UK & Europe)

CAPACITY: Digital DSI - 4 ballasts max

   DALI - 1 ballast max 

WEIGHT: 50g

COLOUR: Silver (part numbers with suffix ‘S’) or White (part numbers with suffix ‘W’)

MATERIAL: Flame retardant PC/ABS

IP RATING: 4X

o

o

OPERATING TEMPERATURE: 0 C to 55 C

2

BLE: 1.5mm  unscreened twisted pair : see Application Note AN4001

At the end of their useful life 

the packaging and product 

should be disposed of via a 

suitable recycling centre.

Do not dispose of with normal 

household waste.

Do not burn.

6.0m

2.5m

Ex-Or 

Novar ED&S LImited

Haydock Lane, Haydock, Merseyside WA11 9UJ
Tel: +44 (0)1942 719229 

Fax: +44 (0)1942 508753

Email: technicalsales.ex-or@honeywell.com

www.ex-or.com

Important Additional Notes

1. A means for disconnection must be incorporated in the fixed wiring in accordance with the current wiring regulations.
2. Although nominally 12V, the dimming output is not SELV and therefore should be treated with the same respect as mains 

with regard to wiring practice.  The 0V line of the dimming output is almost at Neutral potential.

3. The dimming control output should be connected only to the control input of the ballasts - never to other detectors.
4. This equipment should be used to control only those ballasts powered from the same phase as the detector.
5. Do not connect mains to the MLS bus.

2

6. It is imperative that the MLS bus is wired with the correct type of cable; normally it should be 1.5mm  unscreened twisted pair.  

Please read Application Note AN4001 for more details.

7. Due to the fact that the photocell is on the ceiling looking down, it is not possible for measurements made with a lux meter on 

the working plane to remain constant when daylight illuminates the ceiling and the working plane to a differing extent.   

Therefore, products of this type should be regarded as capable of maintaining an APPROXIMATE light level only.

8. This equipment switches lights no more frequently than would a responsible human occupant.  However, manufacturers of 

some particular lighting types (e.g. ‘2D’ luminaires) may specify a maximum number of switching cycles in order to achieve a 

predicted lamp life.  Please check with the manufacturer of the luminaires to ensure that they are compatible with automatic 

controls in this respect.

9. Some devices in this product range feature a silvered surface finish; this is intended for decorative purposes only.  Care 

should be taken to avoid accidental separation of the silvered coating from the product.   If the unit is built into a luminaire 

that is subsequently wrapped in film having adhesive properties, it is recommended that a layer of suitable packaging 

material be used to protect the silvered area.

Summary of Contents for Ex-Or MLS

Page 1: ...d Commissioning Instructions Note HP2000 required for commissioning HC5 or HC6 required for testing MLS Digital Luminaire Controllers MLS2000DIS MLS2000DIW for DSI ballasts MLS2000DALIS MLS2000DALIW for DALI ballasts ...

Page 2: ...mps please ensure that the detector is at the cold end of the lamps In order to achieve satisfactory light level regulating operation a detector must observe a substantially greater proportion of artificial light from the luminaire s under its control than from neighbouring luminaires not under its control This is particularly important when planning the installed layout of linear luminaires that ...

Page 3: ...the OK button toggles between them ii Where there are multiple options a double click of the OK button recalls a list of all options for that parameter Use the UP DOWN and OK buttons to select iii Use the OK button to go forward through the menus without displaying help pages iv Press UPLOAD at any time to transfer all current settings from the handset to the product Please refer to HP2000 instruc...

Page 4: ...rs 4 This equipment should be used to control only those ballasts powered from the same phase as the detector 5 Do not connect mains to the MLS bus 2 6 It is imperative that the MLS bus is wired with the correct type of cable normally it should be 1 5mm unscreened twisted pair Please readApplication NoteAN4001 for more details 7 Due to the fact that the photocell is on the ceiling looking down it ...

Reviews: