Bronze Series LightSpot with photocell

Only suitably qualified personnel should install this equipment.

This is a high-performance presence detector with photocell.  The photocell is designed to hold lights off when 

areas become occupied if the daylight level is high and to switch lights on in occupied areas as the daylight level  

falls.  Please note that the photocell will not switch lights off in areas that are occupied.

Fixing

MS1101PSM - The housing may be secured to a hard surface or a BESA box.  The detector fits into the housing 

with a simple bayonet action.
MS1101PF - Supplied with a sinking (dry lining) box for flush fitting.  Sinking box fits into an 89mm diameter hole 

in ceiling tile or plasterboard ceiling.  To avoid damage to ceiling tile, do not overtighten.  Depth required behind 

ceiling: 62mm from front flange plus an allowance for the minimum bend radius of the cable.  No access above 

the ceiling is necessary.

Note: 

Do not position within 25cm of a luminaire. 

LOAD

(Max 6 Amps)

N

E

L

Permanent 

or switched

supply

N

E

L

Permanent 

or switched

supply

Detector

Detector

Detector

VOLT-

FREE 

OUTPUT

VOLT-

FREE 

OUTPUT

VOLT-FREE 

OUTPUT

LIVE IN

LIVE IN

LIVE IN

NEUTRAL

NEUTRAL

NEUTRAL

EARTH

EARTH

EARTH

Multiple Detectors

Single Detector

LOAD

(Max 6 Amps)

W4228H

The LIVE IN

terminals are

internally linked

External Link

External Link

External Link

Important Additional Notes

1. Only suitably qualified personnel should install this equipment.
2. All terminals on this product are provided for final connections.  It is not intended that the product be used as a junction box 

for looping cables. 

3. A means for disconnection must be incorporated in the fixed wiring in accordance with the current wiring regulations.
4. This equipment switches lights no more frequently than would a responsible human occupant.  However, manufacturers of 

some lighting types (e.g. ‘2D’ luminaires) may specify a maximum number of switching cycles and/or a minimum on-time in 

order to achieve a predicted lamp life.   Please check with the manufacturer of the luminaires to ensure that they are 

compatible with automatic controls in this respect. 

*

LIVE IN

*

LIVE IN

*

LIVE IN

*

LIVE IN

*

*

*

The LIVE IN

terminals are

internally linked

*

Commissioning

The units are supplied with factory default settings (power-up on, fully automatic operation, a 20 minute off delay, 

photocell disabled).  Programme the photocell using the MLS Digital Programmer with LCD display (HP2000), 

or the LightSpot Programmer (HP10).

Off Delay

The Off Delay is set to 20 minutes and is non-adjustable.  A 10-second Off Delay is available for walk testing the 

product.

Walk-test Mode

Walk-test mode is used to check that the detector is operating as required.   The short off-delay enables the 

installer to check that lights are switching on when movements are made at the edge of the detection zone.  It is 

easier to carry out a walk-test when the photocell is not holding the lights off.
1.   Change the programmed Off Delay to 10 seconds using either an HP10 or HP2000.  When using the HP10, 

just press the white button - switch positions are not recognised for this product.  When using the HP2000, 

select Utilities from the main menu, then select Walk Test and press OK.

2.   Move around the area that is being controlled, stopping for 10 seconds to allow the lights to switch off, before 

moving and triggering the lights back on. The Off Delay will reset to its 20 minutes after a five minute period. 

Photocell Operation (Passive/Disabled)

The detector has an in-built photocell. The photocell has two modes of operation - Passive and Disabled.                 

Its operational behaviour is governed by the setting chosen and by the value stored in the threshold.

Passive

 - The photocell will inhibit turn-on of the controlled load if sufficient natural light is available. It will not turn 

the load off whilst an area is occupied

Disabled

 - The photocell has no effect regardless of natural light levels.

Setting the Photocell

1. Wait until the time of day when the ambient light level is equal to the level at which you want the photocell to 

turn on the lights.

2. Using the HP2000, select ‘Set Light Level’ from the Utilities menu and press OK while pointing at the 

detector to store the current light level. The detector stores the value in the Threshold Parameter. This 

procedure can also be accomplished by using the HP10 Basic Programmer’s ‘Store’ button, however editing 

of the stored threshold value is not possible with the HP10.

3.  A numerical value (0-254) is stored in the Threshold parameter (viewable with an HP2000) and can be 

edited if necessary.   A lower value indicates that the area must become progressively darker before the 

controlled lighting will switch ON.  