T7770C or D Wall Module Override LED

The remote override LED, located on either the T7770C or 

T7770D Wall Module will display the Manual Override mode of 

the controller. The modes are:

1.

LED = Off. No override active.

2.

LED = Continuously On. Bypass mode (timed Occupied 

override).

3.

LED = One flash per second. Continuous Unoccupied 

override.

4.

LED = Two flashes per second. Remote only, 

continuous Occupied override.

Step 3. I/O Tests

The controller can be configured using the L

ON

S

PEC

™, or 

E-Vision PC configuration tool. Once this is done, the 

W7751H can be commanded to MANUAL mode, and each 

output and input can be exercised/viewed to verify proper 

wiring connections and equipment operation.

W7751H Actuator Checkout

To check out the actuator on the W7751H, determine the 

direction the damper shaft moves to open the damper (CW or 

CCW). See Fig. 5.

NOTE: Devices for use only if used for Energy Management: 

Q7740A,B and Q7751A.

Devices for use on an Energy Management and/or Smoke 

Control:

— 14507287 Series Power Supplies,

— W7751B2010, W7751D2016, W7751F2011, 

— W7751H2025 Series 9, 

— W7761A2010, 

— Q7750, 

— Q9200, 

— XFL521, XFL522, XFL523, XFL524, 

— XL500, 

— XLINK.

Connect the controller with the laptop PC. To do this, the 

controller on the W7751H must be wired, powered, and 

connected to the portable PC via the SLTA. The SLTA 

connects to the controller on the W7751H via the Jack for 

Network Access on T7770 Wall Modules or by the B-Port on 

the Q7750A Zone Manager. From L

ON

S

PEC

™, or E-Vision 

Software, drive the actuator on the W7751H open and then 

closed. Observe the operation of the actuator; if the damper is 

closed, it should begin to open. If the damper is open, it 

should begin to close.

NOTE: Once finished programming, disconnect the portable 

PC.

If no movement is observed, check to see if 24 Vac is present 

at the controller on the W7751H. With proper wiring, 24 Vac 

present, and proper commands from the software, the 

actuator should operate properly. If not, the W7751H Smart 

VAV Actuator may need to be replaced.

Step 4. Verify Sequences of Operation

For the detailed descriptions of the sequences of operation, 

see the Excel 10 VAV System Engineering form 74-2949.

L

ON

W

ORKS

® and L

ON

T

ALK

® are registered trademarks of Echelon

®

 Corporation.

L

ON

S

PEC

™ is a trademark of Echelon

®

 Corporation.

Summary of Contents for Excel 10 W7751H

Page 1: ...riac output loads must draw a minimum current of 25 mA at 24 Vac 60 Hz nominal Triac maximum current rating 77 mA The actuator on the W7751H mounts directly onto the VAV box damper shaft and has up to 70 lb in torque 8 Nm 90 degree stroke and 90 second timing at 60 Hz The actuator on the W7751H can accommodate the optional field installed auxiliary switches NOTE Mounting thermostat sensor greater ...

Page 2: ...duit NOTE The assembly is intended only for mounting to a horizontal shaft The W7751H actuator is shipped in the fully clockwise CW position 90 degree The W7751H Assembly must be mounted to a horizontal damper shaft to assure proper heat dissipation from the controller housing Mount the W7751H so that the actuator is parallel with the VAV box damper housing In general it is recommended that a wash...

Page 3: ...damper opening angle 45 60 or 90 degrees Fig 5 Determining rotation direction CW or CCW for damper opening If damper shaft diameter is 3 8 inch 10 mm round or square use part 201391 Shaft Adapter shipped with the W7751H Smart VAV Actuator Ensure it is placed opposite set screws See Fig 6 The adapter centers a 3 8 in 10 mm shaft in the hub Failure to use the adapter on a 3 8 in 10 mm shaft causes t...

Page 4: ... yet Before the part no 201614 Range Stop Pin which is shipped with the W7751H Smart VAV Actuator can be inserted in either the 45 or 60 degree CW slot the damper actuator must be driven fully open CCW To do this the controller on the W7751H must be wired powered and connected to the portable PC via the Serial LonTalk Adapter SLTA The SLTA connects to the controller on the W7751H via the jack for ...

Page 5: ...a verified earth ground for each controller in the group See Fig 10 Controller configurations are not necessarily limited to three devices but the total power draw including accessories cannot exceed 100 VA when powered by the same transformer See System Engineering form 74 2949 for power wiring recommendations All loads on an Excel 10 Controller must be powered by a single transformer Keep the ea...

Page 6: ...he portable PC via the SLTA The SLTA connects to the controller on the W7751H via Network Access Jack on the T7770 Wall Module or by B Port on the Q7750A Zone Manager From E Vision Software drive the W7751H actuator and halt the motion at the desired position for switch operation NOTE When installed angular position indicator on the switch face moves from 90 to 0 degrees during CCW motion and from...

Page 7: ...air solid conductor wire For nonplenum areas use CMP listed cable In plenum areas use CMP listed cable Do not bundle output wires with sensor digital input or LONWORKS Bus wires Ensure that neither LONWORKS Bus wire is grounded In noisy high EMI environments avoid wire runs parallel to noisy power cables motor control centers or lines containing lighting dimmer switches Keep at least 3 in 76 mm of...

Page 8: ...T BE TWISTED TOGETHER BEFORE INSERTING INTO THE TERMINAL BLOCK MICROBRIDGE DP SENSOR AIR FLOW DP PICKUP AIR FLOW DIRECTION LOW HI 2 M6410 SERIES 60 VALVE ACTUATOR COM STEM UP STEM DOWN TRIAC EQUIVALENT CIRCUIT TWO OR THREE WAY VALVE SET PT 1 2 3 4 5 6 7 8 9 10 11 12 EARTH GROUND 24 VAC COM OUT 1 OUT 2 E BUS COMM OUT COMM IN 24 VAC NOTE LOAD POWER WIRE IS CONNECTED TO TERMINAL 1 W7751H M10526 1 2 2...

Page 9: ... the Excel 10 FTT Termination Module Installation Instructions form 95 7554 Correct placement of the termination module s is required for proper LONWORKS Bus communications Step 2 Startup Broadcasting the Service Message The Service Message allows a device on the LONWORKS Bus to be positively identified The Service Message contains the controller neuron ID number and therefore can be used to confi...

Page 10: ...appears in one of the following allowable states 1 Off no power to the processor 2 Continuous on processor is in initialized state 3 Slow blink controlling normal state 4 Fast blink when the Excel 10 VAV Controller has an alarm condition When an Excel 10 has an alarm condition it reports it to the central node on the LONWORKS Bus Also the Excel 10 VAV Controller variables AlarmLogX where X is 1 th...

Page 11: ... BLOCK ML7984B REHEAT VALVE ACTUATOR PWM OUTPUT FROM CNTRL PWM H 24 VAC PWM VALVE ACTUATOR 24 N 24 H T6 T5 C B W R SERIES OR PARALLEL FAN CONTACTOR 24 VAC SET PT 1 2 3 4 5 6 7 8 9 10 11 12 24 VAC COM OUT 1 OUT 2 E BUS 24 VAC W7751H M10530 WALL MODULE EARTH GND SENSOR BYPASS LED NOT EARTH GROUND TRIAC EQUIVALENT CIRCUIT 3 2 4 1 1 2 3 4 REVERSE WIRES INCREASE DECREASE TO REVERSE ACTION DIRECT REVERS...

Page 12: ... only if used for Energy Management Q7740A B and Q7751A Devices for use on an Energy Management and or Smoke Control 14507287 Series Power Supplies W7751B2010 W7751D2016 W7751F2011 W7751H2025 Series 9 W7761A2010 Q7750 Q9200 XFL521 XFL522 XFL523 XFL524 XL500 XLINK Connect the controller with the laptop PC To do this the controller on the W7751H must be wired powered and connected to the portable PC...

Reviews: