EXCEL 10 W7751H SMART VAV ACTUATOR

95-7553—04

4

Fig. 6. Use Damper Shaft Adapter for 3/8 in. (10 mm) 

diameter round or square damper shafts.

The W7751H is shipped with the actuator rotated in the fully 

clockwise (CW) position. The installation procedure varies 

depending on the damper direction and angle:

1.

If the damper rotates clockwise 

(CW) to open

, and the 

angle of the damper open to closed is 

90 degrees

manually open the damper fully to the clockwise 

direction and mount the W7751H to the VAV damper 

box and shaft. Tighten the Allen set screws. The part 

no. 201614 Range Stop Pin, which is shipped with the 

W7751H Smart VAV Actuator, is unnecessary. When 

the W7751H closes, the damper rotates 

CCW 90

 

degrees to fully close.

2.

If the damper rotates clockwise 

(CW) to open

, and the 

angle of the damper open to closed is 

45 or 60 degrees

manually open the damper fully to the clockwise 

direction and mount the W7751H to the VAV damper 

box and shaft. Tighten the Allen set screws. Insert the 

part no. 201614 Range Stop Pin, which is shipped with 

the W7751H Smart VAV Actuator, in either the 45 or 

60 degree 

CCW

 slot, whichever applies (see Fig. 7). 

The range stop pin must go all the way through the 

housing. The pin can only be installed in the 

CCW

 slots 

when the actuator is in the 

CW

 position. When the 

W7751H closes, the damper rotates 

CCW

 either 45 or 

60 degrees to fully close.

3.

If the damper rotates counterclockwise 

(CCW) to open

and the angle of the damper open to closed is 

90 degrees

, manually close the damper fully to the 

clockwise direction and mount the W7751H to the 

damper box and shaft. Tighten the Allen set screws. 

The part no. 201614 Range Stop Pin, which is shipped 

with the W7751H Smart VAV Actuator, is unnecessary. 

When the W7751H opens, the damper rotates 

CCW

 90 

degrees to fully open.

NOTE: Be aware that the damper is closed. Until the 

W7751H is powered and the damper is driven 

open, starting the fan system with all the VAV 

box dampers closed can cause duct over-

pressurization and damage.

4.

If the damper rotates counterclockwise 

(CCW) to open

and the angle of the damper open to closed is 

45 or 

60 degrees

, see the following NOTE.

NOTE: Special precautions must be taken for this 

application. Mount the W7751H to the damper 

box. (Do not tighten the Allen set screws yet). 

Before the part no. 201614 Range Stop Pin, 

which is shipped with the W7751H Smart VAV 

Actuator, can be inserted in either the 45 or 60 

degree 

CW

 slot, the damper actuator must be 

driven fully open (CCW). To do this, the 

controller on the W7751H must be wired, 

powered, and connected to the portable PC via 

the Serial LonTalk

®

 Adapter (SLTA). The SLTA 

connects to the controller on the W7751H via 

the jack for Network Access on T7770 Wall 

Module or by the B-Port on the Q7750A Zone 

Manager. From E-Vision Software, drive the 

actuator on the W7751H fully 

CCW

, and insert 

the range stop pin in either the 45 or 60 degree 

CW

 slot, whichever applies (see Fig. 7). The 

range stop pin must go all the way through the 

housing. The pin can only be installed in the 

CW

 slots when the actuator is in the 

CCW

 

position. (Disconnect the portable PC once 

programming has been completed.) Manually 

open the damper shaft fully 

(CCW)

 and then 

tighten the Allen set screws. When the 

W7751H closes, the damper will rotate 

CW

 45 

or 60 degrees to fully close.

Fig. 7. Properly inserting range stop pin.

The Honeywell Software Tool’s (miscellaneous parameter for 

rotation direction) defaults to 

CW to Open

, which applies to 

the damper direction and angle in items 

1

 and 

2

 above. The 

parameter must be changed to 

CCW to Open

 if the damper 

shaft rotates in this direction, which applies to the damper 

direction and angle in items 

3

 and 

4

 above.

IMPORTANT

It is advisable to leave the dampers in an open 

position after W7751H installation to avoid the 

possibility of overpressurizing the ductwork on fan 

startup. Use the De-clutch lever (see Fig. 2 fo

De-clutch lever location) to open the box damper on 

W7751H controllers that are powered down, to 

prevent overpressurization in the ductwork on fan 

startup. To use the De-clutch lever, press and hold 

the lever in the direction of the arrow (this 

disengages the motor). Turn the damper shaft until 

the damper is open and release the lever. When 

power is restored to the W7751H controller, the 

controller synchronizes the damper actuator so that 

the damper is in the correct position upon startup.

When a range stop pin is used with a field-added auxiliary 

switch, the tab on top of the range stop pin must point inward 

toward the VAV damper box shaft. See Fig. 11. This allows 

clearance for the auxiliary switch housing. To remove the pin, 

pry it up with a flathead screwdriver. See Fig. 8.

SHAFT ADAPTER

M2064

CW

CCW

M10002

CCW

CW

45

45

60

60

RANGE

STOP PIN

ACTUATOR 

PLATES

Summary of Contents for Excel 10 W7751H

Page 1: ...riac output loads must draw a minimum current of 25 mA at 24 Vac 60 Hz nominal Triac maximum current rating 77 mA The actuator on the W7751H mounts directly onto the VAV box damper shaft and has up to 70 lb in torque 8 Nm 90 degree stroke and 90 second timing at 60 Hz The actuator on the W7751H can accommodate the optional field installed auxiliary switches NOTE Mounting thermostat sensor greater ...

Page 2: ...duit NOTE The assembly is intended only for mounting to a horizontal shaft The W7751H actuator is shipped in the fully clockwise CW position 90 degree The W7751H Assembly must be mounted to a horizontal damper shaft to assure proper heat dissipation from the controller housing Mount the W7751H so that the actuator is parallel with the VAV box damper housing In general it is recommended that a wash...

Page 3: ...damper opening angle 45 60 or 90 degrees Fig 5 Determining rotation direction CW or CCW for damper opening If damper shaft diameter is 3 8 inch 10 mm round or square use part 201391 Shaft Adapter shipped with the W7751H Smart VAV Actuator Ensure it is placed opposite set screws See Fig 6 The adapter centers a 3 8 in 10 mm shaft in the hub Failure to use the adapter on a 3 8 in 10 mm shaft causes t...

Page 4: ... yet Before the part no 201614 Range Stop Pin which is shipped with the W7751H Smart VAV Actuator can be inserted in either the 45 or 60 degree CW slot the damper actuator must be driven fully open CCW To do this the controller on the W7751H must be wired powered and connected to the portable PC via the Serial LonTalk Adapter SLTA The SLTA connects to the controller on the W7751H via the jack for ...

Page 5: ...a verified earth ground for each controller in the group See Fig 10 Controller configurations are not necessarily limited to three devices but the total power draw including accessories cannot exceed 100 VA when powered by the same transformer See System Engineering form 74 2949 for power wiring recommendations All loads on an Excel 10 Controller must be powered by a single transformer Keep the ea...

Page 6: ...he portable PC via the SLTA The SLTA connects to the controller on the W7751H via Network Access Jack on the T7770 Wall Module or by B Port on the Q7750A Zone Manager From E Vision Software drive the W7751H actuator and halt the motion at the desired position for switch operation NOTE When installed angular position indicator on the switch face moves from 90 to 0 degrees during CCW motion and from...

Page 7: ...air solid conductor wire For nonplenum areas use CMP listed cable In plenum areas use CMP listed cable Do not bundle output wires with sensor digital input or LONWORKS Bus wires Ensure that neither LONWORKS Bus wire is grounded In noisy high EMI environments avoid wire runs parallel to noisy power cables motor control centers or lines containing lighting dimmer switches Keep at least 3 in 76 mm of...

Page 8: ...T BE TWISTED TOGETHER BEFORE INSERTING INTO THE TERMINAL BLOCK MICROBRIDGE DP SENSOR AIR FLOW DP PICKUP AIR FLOW DIRECTION LOW HI 2 M6410 SERIES 60 VALVE ACTUATOR COM STEM UP STEM DOWN TRIAC EQUIVALENT CIRCUIT TWO OR THREE WAY VALVE SET PT 1 2 3 4 5 6 7 8 9 10 11 12 EARTH GROUND 24 VAC COM OUT 1 OUT 2 E BUS COMM OUT COMM IN 24 VAC NOTE LOAD POWER WIRE IS CONNECTED TO TERMINAL 1 W7751H M10526 1 2 2...

Page 9: ... the Excel 10 FTT Termination Module Installation Instructions form 95 7554 Correct placement of the termination module s is required for proper LONWORKS Bus communications Step 2 Startup Broadcasting the Service Message The Service Message allows a device on the LONWORKS Bus to be positively identified The Service Message contains the controller neuron ID number and therefore can be used to confi...

Page 10: ...appears in one of the following allowable states 1 Off no power to the processor 2 Continuous on processor is in initialized state 3 Slow blink controlling normal state 4 Fast blink when the Excel 10 VAV Controller has an alarm condition When an Excel 10 has an alarm condition it reports it to the central node on the LONWORKS Bus Also the Excel 10 VAV Controller variables AlarmLogX where X is 1 th...

Page 11: ... BLOCK ML7984B REHEAT VALVE ACTUATOR PWM OUTPUT FROM CNTRL PWM H 24 VAC PWM VALVE ACTUATOR 24 N 24 H T6 T5 C B W R SERIES OR PARALLEL FAN CONTACTOR 24 VAC SET PT 1 2 3 4 5 6 7 8 9 10 11 12 24 VAC COM OUT 1 OUT 2 E BUS 24 VAC W7751H M10530 WALL MODULE EARTH GND SENSOR BYPASS LED NOT EARTH GROUND TRIAC EQUIVALENT CIRCUIT 3 2 4 1 1 2 3 4 REVERSE WIRES INCREASE DECREASE TO REVERSE ACTION DIRECT REVERS...

Page 12: ... only if used for Energy Management Q7740A B and Q7751A Devices for use on an Energy Management and or Smoke Control 14507287 Series Power Supplies W7751B2010 W7751D2016 W7751F2011 W7751H2025 Series 9 W7761A2010 Q7750 Q9200 XFL521 XFL522 XFL523 XFL524 XL500 XLINK Connect the controller with the laptop PC To do this the controller on the W7751H must be wired powered and connected to the portable PC...

Reviews: