background image

EXCEL 10 W7753A UNIT VENTILATOR CONTROLLER

95-7520—02

4

Fig. 5. Power wiring details for two or more Excel 10s per transformer.

Fig. 6. Transformer power wiring details for one Excel 10 

used in UL 1995 equipment (U.S. only).

Communications

Refer to E-Bus Wiring Guidelines, form 74-2865, for a 

complete description of E-Bus network topology rules. 

Approved cable types for E-Bus communications wiring are 

Level IV 22 AWG (0.34 mm

2

) plenum and non-plenum rated 

unshielded, twisted pair, solid conductor wire. For nonplenum 

areas, U.S. part AK3781 (one pair) or U.S. part AK3782 (two 

pair) can be used. In plenum areas, U.S. part AK3791 (one 

pair) or U.S. part AK3792 (two pair) can be used. 

Communications wiring can be run in a conduit, if needed, 

with 

non-switched

 24 Vac or sensor wiring. If a longer E-Bus 

network is required, a Q7740A 2-way or Q7740B 4-way 

repeater can be added to extend the length of the E-Bus. Also 

a Q7751A Router can be added to partition the system into 

two segments and effectively double the length of the E-Bus. 

Only one router is allowed with each Excel 10 Zone Manager, 

and each network segment can have a maximum of one 

repeater.

Pull the cable to each device on the E-Bus and connect to 

communication terminals 14 and 15 (W7753A).

NOTES: (For Communications Wiring)

All field wiring must conform to local codes and 

ordinances (or as specified on the installation 

drawings).

Approved cable types for E-Bus communications 

wiring is Level IV 22 AWG (0.34 mm

2

) plenum 

and non-plenum rated unshielded, twisted pair, 

solid conductor wires. For nonplenum areas, U.S. 

part AK3781 (one pair) or U.S. part AK3782 (two 

pair) can be used. In plenum areas, U.S. part 

AK3791 (one pair) or U.S. part AK3792 (two pair) 

can be used.

Unswitched 24 Vac power wiring can be run in the 

same conduit as the E-Bus cable.

Do not bundle output wires with sensor, digital 

input or communications E-Bus wires.

Do not use different wire types or gauges on the 

same E-Bus segment. The step change in line 

impedance characteristics would cause unpre-

dictable reflections on the E-Bus. When using dif-

ferent types is unavoidable, use a Q7751A Router 

at the junction.

In noisy (high EMI) environments, avoid wire runs 

parallel to noisy power cables, motor control cen-

ters, or lines containing lighting dimmer switches, 

and keep at least 3 in. (76 mm) of separation 

between noisy lines and the E-Bus cable.

Each daisy-chained E-Bus segment that is on one 

side of a Q7751A,B Router (can contain up to 60 

Excel 10s) and has a length greater than 1640 ft. 

(500m) must have two E-Bus 209541B 

Termination Modules, one at each end of the 

daisy-chain wiring run.

Make sure that neither of the E-Bus wires is 

grounded.

NOTE: If a 209541B Termination Module is required at a the 

UV controller, connect two of the three termination 

module wires to the E-Bus terminals. Selecting the 

appropriate two wires depends on the E-Bus network 

topology. Refer to the E-Bus Wiring Guidelines, form 

74-2865, and the Excel 10 FTT Termination Module 

Installation Instructions, form 95-7554. For example, 

using a doubly terminated daisy-chained bus topol-

ogy, if controllers are on either end of an E-Bus wire 

run, mount the termination module on the appropri-

ate terminals as shown in Fig. 7.

M12682

24 VAC

120/240 VAC

TRANSFORMER

W7753A

EARTH

GROUND

24

25

1

W7753A

EARTH

GROUND

24

25

1

W7753A

EARTH

GROUND

24

25

1

M12680

24 VAC

LINE VOLTAGE

GREATER

THAN 150 VAC

TRANSFORMER

W7753A

EARTH

GROUND

EARTH

GROUND

IF THE W7750 CONTROLLER IS USED IN UL 1995 EQUIPMENT AND THE 

PRIMARY POWER IS MORE THAN 150 VOLTS, GROUND ONE SIDE OF 

TRANSFORMER SECONDARY.

1

1

1

Summary of Contents for EXCEL 10 W7753A

Page 1: ...7753A Controller communicates via the 78 kilobaud Echelon LonWorks E Bus Network Allowable input output connections consist of wall module points plus two additional resistive sensor inputs two voltage current inputs four digital inputs and eight digital Triac outputs For the W7753A any hardware driven by the Triac outputs must have a minimum current draw when energized of 25 mA and a maximum curr...

Page 2: ...lastic cover Use the screws appropriate for the mounting surface The W7753A can be mounted in any orientation Ventilation openings were designed into the cover to allow proper heat dissipation regardless of the mounting orientation The W7753A can also be mounted using DIN rail obtain locally If using DIN rail also purchase from Augat Inc part number 2TK2D DIN rail adapter two each See Fig 3 Fig 2 ...

Page 3: ...II restrictions U S only transformers must not be larger than 100 VA A transformer that meets CE mark requirements and that meets the Low Voltage Directive LVD requirements must be used in Europe for all installations of this product More than one W7753A Controller can be powered by a single transformer Fig 4 shows power wiring details for a single controller and Fig 5 depicts multiple controllers...

Page 4: ...o pair can be used Unswitched 24 Vac power wiring can be run in the same conduit as the E Bus cable Do not bundle output wires with sensor digital input or communications E Bus wires Do not use different wire types or gauges on the same E Bus segment The step change in line impedance characteristics would cause unpre dictable reflections on the E Bus When using dif ferent types is unavoidable use ...

Page 5: ... Wiring Details The W7753A Controller has the terminal arrangements shown in Fig 9 through 14 Connection for operator access to the E Bus is provided by plugging the Serial LonTalk Adapter SLTA connector into the E Bus jack NOTE If an Excel 10 Controller or Zone Manager is not connected to a good earth ground the controller internal transient protection circuitry is compromised and the function of...

Page 6: ...ET 2 7 8 5 6 9 10 LED SET PT FAN BYPASS 1 2 3 4 5 6 7 8 E BUS 24 VAC W7753A UNIT VENTILATOR CONTROLLER 1 2 1 2 3 3 3 EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM USE THE HEAVIEST GAUGE WIRE AVAILABLE UP TO 14 AWG 2 O MM2 WITH A MINIMUM OF 18 AWG 1 O MM2 FOR EARTH GROUND WIRE TO ASSURE PROPER ELECTRICAL CONTACT WIRES MUST BE TWISTED TOGETHER BEFORE INSERTION INTO THE TERMINAL BLOCK CONTACTS...

Page 7: ...1 OUT 7 OUT 6 OUT 5 OUT 4 OUT 8 OUT 1 OUT 3 OUT 2 DI 2 DI 4 DI 1 DI 3 GROUND PNEUMATIC VALVE M12693 GROUND M B M 1 2 3 4 5 6 7 8 E BUS 24 VAC W7753A UNIT VENTILATOR CONTROLLER 1 2 E BUS E GND GND SNSR SETPT LED BYPASS GND GND 9 10 11 12 14 J3 15 31 30 29 28 27 26 25 24 23 22 21 20 24 VAC COM E BUS JACK 22 VDC OUT 19 18 17 16 AI 1 OHM AI 2 OHM AI 4 V mA OUT 7 OUT 6 OUT 5 OUT 4 OUT 8 OUT 1 OUT 3 OUT...

Page 8: ...nd ordinances or as specified on installation wiring diagrams Fig 14 Typical 2 to 10 Volt DC humidity sensor to W7753A For note 2 refer to Fig 8 1 2 3 4 5 6 7 8 E BUS 24 VAC 1 2 E BUS E GND GND SNSR SETPT LED BYPASS GND GND 9 10 11 12 14 J3 15 31 30 29 28 27 26 25 24 23 22 21 20 24 VAC COM E BUS JACK 22 VDC OUT 19 18 17 16 AI 1 OHM AI 2 OHM AI 4 V mA OUT 7 OUT 6 OUT 5 OUT 4 OUT 8 OUT 1 OUT 3 OUT 2...

Page 9: ...roadcasting the Service Message The Service Message allows a device on the E Bus to be positively identified The Service Message contains the controller ID number and therefore can be used to confirm the physical location of a particular Excel 10 in a building There is one method of broadcasting the Service Message from an Excel 10 W7753A Controller This uses a hardware push button on the side of ...

Page 10: ...cycled or the node is reset The alarm is not issued until FanFailTime seconds have elapsed since the loss of flow condition was first reported DIRTY_FILTER 7 The pressure drop across the filter exceeds the limit and the filter requires maintenance The control runs normally SMOKE_ALARM 8 The smoke detector has detected smoke and the node has entered an emergency state IAQ_OVERRIDE 9 The indoor air ...

Page 11: ...EXCEL 10 W7753A UNIT VENTILATOR CONTROLLER 11 95 7520 02 ...

Page 12: ...nal Inc 95 7520 02 K K Rev 03 09 Automation and Control Solutions Honeywell International Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Toronto Ontario M1V 4Z9 Honeywell GmbH Böblinger Straße 17 D 71101 Schönaich customer honeywell com ...

Reviews: