10

ON

1 2 3 4

Switch 4 = ON

Maintained operation

(default position)

ON

1 2 3 4

Switch 4 = OFF

Non-maintained 

operation

7

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

1h

(default position)

3h

8h

Step 7

: The control of maintained or non maintained operation of the luminary is achieved through Switch 

4  of  DS1.  For  maintained  operation,  switch  number  4  must  be  in  ON  position.  For  non-maintained 
operation, switch number 4 must be in OFF position.
The user can select one of the 3 available minimum autonomy durations: 1 hour, 3 hours and 8 hours. The 
selection must be done while the luminaire is disconnected from AC and battery supplies. The selection is 
achieved through Switches 2 & 3 of  DS1. Switch 1 is not used.

Step 8:

  Slide the two aluminium parts carefully together.

Step 9:

  Fasten the two screws (included) as shown in the picture.

Step 10:

  Fasten the two screws (included) as shown in the picture.

Two additional labels are included in the package, one for 3 hour duration (180) and one for 8 hour duration 
(480). Depending on the selected duration, the installer must cover the default 1 hour (60) printing with 
one that has the required duration.

Note: 

In case of battery replacement, this must be replaced with parts of the same type and characteristics. 

The replacement must be performed by the manufacturer or a competent person.

Note: 

If the supply cable of the luminaire is damaged, it shall exclusively be replaced by a competent person 

in order to avoid hazard.

Note: 

In case of mains power disconnection for a period of more than two months, the battery must be 

disconnected. 

Important  notice  when  installing  luminaires  within 
the same area!!!

To avoid that luminaires perform their battery test at 
the same day, connect the battery packs with more 
than 1,5 minutes inbetween.

7

8

9

Indicator LEDs

LED Status explanation

Description

GREEN

YELL

OW

RED

Normal

Charging  (battery test not possible while charging

Mains off, battery not connected or charger fault

Battery fault

Battery test

Light source test

Light source fault

Battery fault and light source fault

Off

On

Flashing

At the end of their useful life the packaging, product 
and  batteries  should  be  disposed  of  via  a  suitable 
recycling centre. Do not dispose of with your normal 
household waste. Do not burn.