7. C300 Controller Operation
7.5. Activate C300 Controller's CEE
R500
April 2017
Series 8 C300 Controller User's Guide
Honeywell
191
7.5
Activate C300 Controller's CEE
For the controller to begin executing its control strategy, you must activate the CEEC300
block.
Initial activation order guidelines
Make the initial activation of control strategy components in Control Builder from the
Monitoring tab in the following suggested order to minimize possible bad data generated
alarms.
Order
Component
1
Control environment components such as:
CEEC300
2
Series 8 Input/Output Modules (IOMs)
3
Control Modules (CMs) and/or Sequential Control Modules (SCMs)
Activating the CEE
To activate the CEEC300 block, perform the following steps.
Step
Action
1
From the Monitoring Tree, right-click CEE.
2
Click
Change State
.
3
Click
Yes
from the pop-up window to set the selected item active.