7. C300 Controller Operation
7.5. Activate C300 Controller's CEE
190
Series 8 C300 Controller User's Guide
Honeywell
R500
April 2017
Step
Action
The CEE turns green on the Monitoring Tree.
Remember that the CEE must be active for anything assigned to the CEE
to work. Even if a CM is active, it will not do anything unless the CEE is
also active.
Alternate methods:
Click the Toggle State toolbar button
to set the selected item active.
Select
Operate
>
Change
State…
Setting the CEE inactive
To set the CEE inactive, perform the following steps.
Step
Action
1
From the Monitoring Tree, right-click CEE.
2
Click
Change
State…