3. C300 Controller Installation and Upgrades
3.2. C300 Controller installation
R500
April 2017
Series 8 C300 Controller User's Guide
Honeywell
35
Considerations
When installing a redundant controller pair consisting of a primary and a partner
secondary controller:
The secondary controller should be installed in the same cabinet as the primary
controller.
The secondary controller may be installed on a separate channel from the primary
controller.
To install a C300 Controller, perform the following steps.
Step
Action
1
Refer to appropriate site location drawings for the specified controller
installation location, controller Device Index (FTE address) and wiring
diagrams.
2
Identify the mounting location on channel and align mounting holes in IOTA
with screw hole locations on the channel.
3
Be sure component side of IOTA is facing up. Refer to the figure below.
Assemble mounting screws, washers and spacers provided. Insert spacers
and washers between backside of IOTA and front of channel.