5. C300 Configuration Form Reference
5.1. C300 Controller Block
R500
April 2017
Series 8 C300 Controller User's Guide
Honeywell
93
Plain Text
Parameter Name
User
Configurable
Notes
Redundancy
Compatibility
No
Shows redundant partner
compatibility.
Inhibit Sync Reason
No
Shows the reasons for
inhibiting initial-sync.
Initial Sync Progress
(%)
No
Shows current
synchronization progress
in percent.
Last Synchronization
Time
No
Shows system time when
initial synchronization was
completed.
Last Loss of Sync
Time
No
Shows system time when
last synchronization was
lost.
Redundancy
Controllability
RDNCTLABILITY
No
Shows whether the current
controller is better, equal,
or worse to be the primary
controller (as compared to
the partner controller).
Device Index
RDNDEVICEIDX
No
Shows the Device Index of
the redundant secondary
controller.
Redundancy Statistics
Redundancy Traffic
(bytes/sec)
RDNXFERAVG
No
Current amount of
redundancy data traffic
across the redundancy
private path, in bytes per
second.
Max Redundancy
Traffic (bytes/sec)
RDNXFERMAX
No
Maximum amount of
redundancy data traffic
across the redundancy
private path throughput
since power up or last
statistics reset.