6. Load C300 Controller Configuration
6.4. Load With Contents command
170
Series 8 C300 Controller User's Guide
Honeywell
R500
April 2017
6.4
Load With Contents command
When you choose
Tools
>
Load with Contents
from the Tools menu, the Load Dialog
box shows the selected component and any objects, (IOMs, CMs, and so on.) that are
contained by the selected component. For example, when a CEEC300 block is selected
for loading, the Load Dialog will list all the objects assigned to (or contained by) that
CEE in the dialog window. You can then select (or deselect) the objects that you want to
load.
6.5
Reloading components from project
Reload of component configuration may be necessary especially when you make changes
to the component or function block configuration, or after you replace a failed field
device, I/O module or controller. You can use the applicable previous load procedure to
re-load data to components from the Project or Monitor tab. It is good idea to invoke the
following commands through the Controller menu after a reload operation.
(perform first), and then
Update to Project
Restrictions and conditions for reloading operations
Re-loading parameter data to certain function blocks may incur some restrictions or
conditions with other related blocks. The following table lists conditions to consider
when re-loading previously loaded blocks.
Block to be
Re-Loaded
Conditions or Restrictions
Series 8
IOMs
Channel blocks that are assigned and have not been previously
loaded, will not be loaded.
CM
The C300/CEE, IOLINK and IOMs whose channels are assigned
to the CM must be previously loaded.
The CM reload operation loads the CM block and any assigned IO
Channel blocks to the associated CEE.
CM reload fails if any of the following errors are encountered:
The I/O Channel's associated IOM block has not been
previously loaded.
The CEE block is not present and loaded.
The C300 block is not present and loaded.