Attention:
Notifications coming in as a result of the alarm recovery operation may cause the
Alarm Summary to overflow again. Steps should be taken to reduce the number of
active alarms prior to attempting recovery.
Example scenarios
Experion cluster
Server
ES -C
Console
Station
ES -CE
Extension
Station
FLEX
Station
Controller
FTE
n
If an alarm overflow occurs on a cluster server, clicking the Recover
Alarms button will cause alarm recovery on the server.
n
If an alarm overflow occurs on a Console Station, clicking the Recover
Alarms button will cause alarm recovery on the Console Station.
n
If an alarm overflow occurs on both the cluster server and a Console
Station, clicking the Recover Alarms button on the Console Station will
cause alarm recovery on both the server and console.
Responding to alarms
Honeywell 2017