Alarm
Description
Profibus PA slave fault alarm
This alarm is reported by the GENPADSB if any of the following
diagnostics is active:
•
DIA_HW_ELECTR
•
DIA_HW_MECH
•
DIA_TEMP_MOTOR
•
DIA_TEMP_ELECTR
•
DIA_MEM_CHKSUM
•
DIA_MEASUREMENT
•
DIA_NOT_INIT
•
DIA_INIT_ERR
•
DIA_ZERO_ERR
•
DIA_SUPPLY
•
DIA_CONF_INVAL
•
DIA_WARMSTART
•
DIA_COLDSTART
•
DIA_MAINTENACE
•
DIA_CHARACT
•
IDENT_NUMBER_VIOLATION
•
EXTENSION_AVAILABLE
Module fault in PA network
This alarm is reported by the GENPAGWDSB if any of the module/
slot referred by the PDC configuration has diagnostic data, is failed, or
has status that is not “Module OK”.
Profibus PA Gateway fault
This is alarm is reported by the GENPAGWDSB if the gateway status
indicates “Configuration fail” or “Invalid bus parameter.”
Profibus PA slave fault
This alarm is reported by the GENPAGWDSB if any of the slaves in
the PA network report slave or channel-based diagnostics.
Diagnostic data is corrupted
This alarm is reported by the GENPAGWDSB if the structure of the
IM-157 diagnostic data is corrupted.
Data status below limit in PDC <PDC number>
This alarm is reported by the GENPADSB and/or the GENPAGWDSB
whenever the channel status is below the defined first acceptable PA
status value.
For this alarm to be reported, you must define the first acceptable PA
status value while configuring the GENPADSB and/or
GENPAGWDSB.
7 DEVICE SUPPORT BLOCK (DSB)
177
Summary of Contents for Experion PKS
Page 1: ...Experion PKS PROFIBUS Gateway Module User s Guide EPDOC XX88 en 431E June 2018 Release 431 ...
Page 8: ...CONTENTS 8 www honeywell com ...
Page 10: ...1 ABOUT THIS GUIDE 10 www honeywell com ...
Page 32: ...4 PROFIBUS GATEWAY MODULE PGM INSTALLATION 32 www honeywell com ...
Page 58: ...5 PROFIBUS GATEWAY MODULE PGM BLOCK 58 www honeywell com ...
Page 69: ...6 PROTOCOL BLOCK 69 ...
Page 103: ...5 Click OK 6 PROTOCOL BLOCK 103 ...
Page 110: ...6 PROTOCOL BLOCK 110 www honeywell com ...
Page 183: ...PDC Details tab Figure 6 Detail Display of PDC Details tab 7 DEVICE SUPPORT BLOCK DSB 183 ...
Page 186: ...7 DEVICE SUPPORT BLOCK DSB 186 www honeywell com ...
Page 231: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 231 ...
Page 232: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 232 www honeywell com ...
Page 236: ...10 PROFIBUS GATEWAY MODULE PGM CONFIGURATION EXAMPLE 236 www honeywell com ...
Page 264: ...13 PROFIBUS GATEWAY MODULE PGM TROUBLESHOOTING 264 www honeywell com ...